Weil-McLain EGH-105, EGH-125 manual VIII Check-outprocedure - troubleshooting, Secure connections

Models: EGH-125 EGH-105

1 36
Download 36 pages 3.24 Kb
Page 28
Image 28
Secure connections.

EGH-105 to EGH-125 Control Supplement

VIII Check-out procedure — troubleshooting

TS-2: No Spark — System (boiler with vent damper) does not work

 

 

 

 

Secure connections.

 

 

 

 

 

Is damper harness securely plugged in at both ends?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check for loose wire connections or bad relay on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transformer.

 

 

 

 

 

Is 24VAC present across transformer terminals C & Y?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check for open thermostat, circulator relay, operating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

control, limit control or LWCO. Check the CSD-1 control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is 24VAC present across terminal C and yellow wire on

 

panel, impulse relay and push-button switch.

 

 

 

 

 

 

 

 

 

damper connector?

 

 

 

If limit controls or water level controls

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

Yes

 

 

 

lockout on manual reset, determine cause

 

 

 

 

 

 

 

 

 

and correct condition. Failure to do so could

 

 

 

 

 

 

 

 

 

 

 

 

 

 

result in severe personal injury, death or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is damper rotated open?

 

 

 

substantial property damage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check for out of round stack section. Does motor rotate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

open?

 

 

 

 

 

Is 24VAC present across terminals PV and MV/PV?

 

 

No

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace actuator.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is spark present now?

 

 

Retest.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open thermostat contacts for 30 seconds. Damper will

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Retest.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rotate to closed position. Close thermostat contacts.

 

Damper will rotate to open position. Is 24VAC present

 

 

 

 

 

 

 

Turn OFF supply voltage.

 

 

 

 

 

across terminals PV and MV/PV?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical shock hazard. Failure to turn off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

power before proceeding could cause

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

severe personal injury or death.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check continuity of each wire in wiring harness to

 

 

 

 

 

Securely connect

 

 

 

 

 

 

Check spark wire. Is it securely

 

 

 

 

 

 

 

 

 

 

 

 

connected to ignition control?

 

damper. Does continuity exist for each wire?

 

 

 

 

 

and turn ON supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

voltage. Retest.

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

Yes

 

 

No

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace damper

 

 

Remove damper harness from

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is condition of spark wire good

 

 

wiring harness.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(not brittle, burned or cracked)?

 

 

 

 

boiler wiring harness.

 

 

 

 

Replace pilot

 

 

 

 

 

 

 

 

 

Retest.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMPORARILY install jumper

 

 

 

 

assembly. Retest.

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

between terminal 2 and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace ignition

 

 

terminal 5 on damper plug in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

control. Retest.

 

 

boiler wiring harness. See

 

 

 

 

Is spark gap 0.125" and

 

 

 

 

 

Is spark electrode

 

 

 

 

 

 

 

 

figure below. Does boiler fire?

 

 

 

 

located in pilot gas stream?

 

 

 

ceramic cracked?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

Yes

 

 

 

 

 

No

 

 

 

Yes

 

 

 

 

 

 

 

 

 

No

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace pilot

 

 

 

 

 

 

 

 

 

Replace ignition

 

 

 

Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pilot

1

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

assembly.

 

 

 

 

 

 

 

 

 

control. Retest.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

assembly.

 

 

Temporary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

jumper

 

Replace damper

 

 

 

 

 

Turn ON supply voltage and operate

 

 

 

 

 

 

4

5

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

actuator. Retest.

 

 

 

 

 

system several complete cycles.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

Part Number 550-110-677/0299

Page 28
Image 28
Weil-McLain manual VIII Check-outprocedure - troubleshooting, EGH-105to EGH-125 Control Supplement, Secure connections