INSTALLATION CHECKS
Follow these instructions to ensure proper startup and confirm that the installation is correct.
1.Check to make sure Invert and Charge are OFF. The INVERT LED should not be illuminated, the CHARGE LED should be blinking (charger ready but no external AC power available). If using a Remote Control Panel or a Link Instrument, make sure inverter and charger indicators are OFF.
2.Check battery polarity. If the unit was connected to the battery with reverse polarity, the unit will be damaged.
3.Check the battery voltage and ensure it is within proper range for the unit
Do not apply shorepower or generator power without performing the following steps:
1.Test the inverter function:
•With no loads connected to the output of the inverter, turn the INVERT Switch ON. The INVERT LED should be solid green. If using a remote, turn ON the inverter with the switch on the Remote Control Panel or Link Instrument.
•The Freedom unit will produce a slight ticking. If using a Remote Control Panel or Link Instrument the INVERT LED will illuminate and the voltage indicator will display the battery voltage. The DC Amps LED will not be lit be- cause the unit is in the idle mode.
•Add a load of 7 watts or more to the output of the inverter. A 40 watt incandescent light bulb will work fine. The DC Amps LEDs on the remote will indicate the DC draw from the bat- tery through the inverter.
WARNING
Do not turn the inverter ON before eliminating any possibility of backfeed.
•Leave the load connected and turn OFF the INVERT mode by pressing the INVERT switch or turn OFF the INVERT mode from the Remote Control Panel or Link Instrument.
2.Test the transfer function:
•Be sure the unit is OFF, the INVERT and CHARGE LEDs are not illuminated. Apply shorepower. If there is a backfeed in the installation, the unit will protect
•Once shorepower has been applied to the unit, there will be approximately an
37