![](/images/backgrounds/92630/92630-4828x1.png)
INSTALLATION
Battery Cable FusingA fuse is required by the NEC to protect the battery and cables. A UL Listed DC rated slow blow fuse must be installed in the positive (+) battery cable, within 18 inches of the battery.
Recommended Fuse: UL Listed Class T JLLN with a DC Rating. This fuse with fuse holder is available from your dealer.
For the
350 Amp Fuse & Holder PN#
350 Amp Fuse Only PN#
HARDWARE
_
+
+ (red)
COMPRESSION / RING TERMINAL | EXPLODED VIEWS |
| ||
| NUT | OF FUSE ASSEMBLY |
| |
|
| RING / RING TERMINAL | ||
| LOCK WASHER |
| ||
|
| NUT | ||
| FLAT WASHER |
| ||
|
| LOCK WASHER | ||
| BATTERY |
| ||
INVERTER |
|
| ||
CABLE |
| FLAT WASHER | ||
CABLE | INVERTER | |||
| BATTERY | |||
| FUSE | CABLE | ||
|
|
| CABLE | |
| FUSE HOLDER |
| FUSE | |
|
|
|
WARNING
Improper stack up of hardware will cause excessive heat and fuse failure. Stack up as shown.
FUSE HOLDER
28