OPERATION

When the LED is blinking slowly (once per second), an over-current condition or a short circuit has occured. The system has shut OFF and will not automatically restart. Correct the fault condition and manually restart the system.

LOW BATTERY & OVERTEMP/OVERLOAD

-Red LEDs

When both LEDs are blinking, an AC backfeed has been detected. A backfeed occurs when AC power from an external source is connected to the output of the inverter. Inspect wiring for a possible input/output wiring error. This condition will damage the unit and must be corrected before further operation.

TSC (Temperature Sensitive Charging)

This provides for the connection of a sensor to measure battery temperature for compensated charging. If no sensor is connected the charge voltage levels are set to defaults based on battery type.

OPTIONAL REMOTES

If using a remote, refer to the installation instructions included with the remote.

Note: When a Remote Control Panel is installed, the jumper included in the parts plastic bag is not used in the Auxiliary Switch Port (AUX SWITCH) on the front panel of the inverter/ charger. See page 23 for more details.

 

Overtemp

 

Low

Remote TSC

Auxiliary Port

Battery

 

9