MICROPROCESSOR RESET PROCEDURE
The LINK 2000 uses a microprocessor to perform all of its calculations and functions. We have worked very hard to ensure a stable,
TO RESET FROM A LOCKUP, ERRATIC DISPLAY, OR ERRATIC BEHAVIOR
1) | Disconnect from shorepower. |
2) | |
| is jumpered to the blue or violet wires, remove the fuses in the appropriate wire |
| to remove power to the unit. If your meter is an alternator regulator model you |
| can |
| terminal board and reconnecting it. |
3) | Wait at least 30 seconds before reconnecting the fuse (or the ribbon cable). |
| When the fuse is reconnected use a continuous motion. If the meter is |
| intermittently powered and |
| microprocessor may lock up. |
4) | Press the INVERT and CHARGE buttons so that their LEDs are illuminated. |
5) | Restore shorepower. After a few seconds you should see the AC STATUS |
| light illuminate and the charge status lights come on indicating the CHARGE |
| mode. (If the battery is full the CHARGE light will only be on for a short time |
| before the Accept LED comes on.) |
6) | Check to see that your battery capacity, battery type, ambient temperature, |
| Peukert's exponent, charged voltage parameter, and any other values you |
might have previously set up are still correct. If they are, end here; if not, change them to the appropriate values or follow the procedure on the next page for resetting to factory values.
30