Freedom units produced prior to serial #100,000 have temperature compensation only for warm or cool environments. The temperature setup sets the voltages as per below:
TEMP | TYPE 0 (Liquid) | TYPE 1 (Gel 1) | ||||
| Accept | Float | Equalize | Accept | Float | Equalize |
Above 80 °F | 13.9 | 13.3 | 15.8 | 14.1 | 13.8 | 14.1 |
Below 80 °F | 14.4 | 13.5 | 16.3 | 14.4 | 13.8 | 14.4 |
F04 - TOGGLE DISPLAY BETWEEN AHR AND KWHR
DEFAULT OFF = Ah DISPLAY MODE
ON = Ah/kWh ALTERNATING DISPLAY MODE
When this function is selected theAhrs display alternates between the normal amp- hour mode and the
F05 - ALTERNATIVE ENERGY MODE
DEFAULT: OFF
ON = USE ALTERNATIVE ENERGY DEFAULTS
Turn this mode on if your Link 2000 is used in Alternative Energy Systems. This function 1) reduces the time necessary to satisfy the charged parameters from five minutes to one minute; 2) sets Batt #2 discharge floor to 100%; 3) prevents Batt #2 from doing Ah resets; 4) changes Charged V parameter to 13.5 V (27 V). If you're using a semi- mechanical photovoltaic controller, we strongly suggest you also consider changing Charged Current to 4%.
F06 - MANUALLY SET CEF (NOT RECOMMENDED) DEFAULT OFF = AUTO RECALCULATION OF CEF DISPLAY = A87 OR A90 (DEPENDS ON BATTERY TYPE) RANGE =
Allows manual set up of CEF (Charge Efficiency Factor). Default display A87 or A90 (depending on battery type
F07 - SET TEMPERATURE COEFFICIENT
DEFAULT = 0.5 RANGE =
This factor compensates for capacity change with temperature. Typical value 0.5% Capacity/°C. This coefficient must be supplied by the battery manufacturer. The default value is typical for lead acid liquid or gelled batteries. Normally this value is not changed.