F13 SET DISCHARGE FLOOR

 

DEFAULT = 100% RANGE = 50%–100%

STEP = 5%

When this option is activated, you may set a discharge floor for each battery bank. When the discharge floor is set to 50%, the Time Remaining display reports time remaining until the battery reaches the 50% discharged level. You may set the discharge floor from 50%to100%in5%increments.WhentheSettableDischargeFlooris100%,time remaining to 100% discharge is displayed. You may set a discharge floor for each battery. The settable floor is applied to the battery selected (BAT1 or BAT2) at the time you enter this function. You may wish to set a higher discharge floor, such as 50%, for an engine starting bank and a deeper floor, such as 75%, for a deep-cycling house bank.

F14 - ACTIVE TEMPERATURE COMPENSATION ON, OFF

DEFAULT = OFF RANGE = OFF, ON

When this function is ON, the Link 2000/Link 2000-R uses the actual battery temperature reported from the Freedom Inverter/Charger through the temperature probe. If the unit Inverter/Charger does not report a valid temperature reading, the Link 2000 will use the battery temperature declared by F03 (Default: 70 °F) to set charging voltages. Remember: charging voltages are controlled by battery type and temperature settings.

F15 - SPECIAL FUNCTION FOR DIAGNOSTIC USE.

DEFAULT ON = INVERTER CONTROL OFF = ASCII OUTPUT

CAUTION!! LEAVE THIS FUNCTION ON. TURNING IT OFF DISABLES COMMUNICATION. TO BE USED FOR SERVICE DIAGNOSTIC PURPOSES ONLY.

SUMMARY OF SOFTWARE DEFAULTS

 

 

Function

Name

Default

Options

 

F01

Averaging Period

0

4, 16, 32 minutes

**

F02

Battery Type

Lead Acid

Gel cell , AGM

**

F03

View or set ambient

70 °F

See text

 

 

temperature

 

 

 

F04

View Ah or kWh

OFF (Ah)

ON (kWh)

 

F05

Alternative Energy mode

Off

Solar cell (see text)

 

F06

Peukert's Exponent

Auto

See text

 

F07

Temp Coefficient

0.5

0.1 to 0.9

**

F08

Puekert's Exponent

1.25

1.00 to 1.50 (see text)

 

F09

% remaining time display

Off (Ah mode)

On (% remaining)

 

F10

AlternatorCurrentlimit

100 amps

30 to 220 amps, off

 

F11

Battery #2 used for control

On (Yes)

Off

 

F12

Backlightingintensity

130

0 to 240

 

F13

Settable discharge floor

100%

50% to 100%

 

F14

Active Temp Compensation

Off

On

 

F15

Manufacturer Reserved

On

Do not change

** Item that should be confirmed or changed at installation to ensure proper operation

14