INVERTER SETUP

IDLE MODE: The default value is 4 watts. This means it takes a 4-watt AC load to turn the inverter on from its low power idle mode. Setting a value of 0 watts means the inverter is always on. The low power idle current is about 0.25 amps. When idle mode is set to 0 W the current consumption goes up to about 0.9 amps. Range = 0 W, 4 W, 6 W, 15 W. (0–15 watts in 5-watt steps in Series 458 units.)

SETUP EXAMPLE: To set the IDLE MODE to 0 watts, first select the INVERT on, then press the SETUP BUTTON until the Green LED begins to flash. Now, press and hold the IDLE MODE BUTTON. The present value will appear. The display will scroll afterthreeseconds.Holdthebuttondownuntil0appears.Releasethebutton.Thenewvalue will remain in the display for about five seconds. When the display reverts to the normal monitoring function the new value is stored in nonvolatile memory. To see if the new value has been successfully stored, repeat the setup procedure but do not scroll to a new value.

PWR SHARE: The default value is 30 amps (or OFF for Freedom 25). The power sharing feature automatically reduces the charger output, and therefore the AC power consumption, if the load passing through the inverter's automatic transfer switch exceeds the setup value. This load management feature helps prevent AC supply breakers from tripping when boats or RVs are plugged into AC power and the charger, water heater, and perhaps other loads all come on at once. In "Off Grid" applications the auxiliary generator often has several jobs—water pumping, running the washing machine, or heavy power tools—in addition to supplemental battery charging. With Power Sharing, when a heavy load turns on, it reduces charger output to help supply the heavy load. The ranges below are for units with serial numbers greater than 100,000:

Freedom 10, 15 & 20 Range = 5, 15, 20, 30 A; Freedom 25 & 30 Range = 5, 20, 30 A, OFF; Freedom 10E & 20E Range = 2, 5, 10, 15 A; Freedom 25E Range = 2, 10, 15 A, OFF

For Freedom serial numbers below 100,000 use this table to interpret the display.

Model

F10

F10

F10E

F10E

F20

F20

F25

F25

Serial#

<70759

>70760

<71746

>71747

<70699

>70700

<70801

>70802

Display

Amps

Amps

Amps

Amps

Amps

Amps

Amps

Amps

0

30

30

15

15

30

30

OFF

OFF

1

20

20

10

10

20

20

50

30

2

15

15

7.5

7.5

15

15

30

20

3

10

5

5

2

10

5

20

5

For Series 458 units, the range is 0–50 amps, settable in 5-amp steps.

ANOTHER SETUP EXAMPLE: To set PWR SHARE to 20 amps on a F10 Model with a serial number below 100,000, first select the CHARGE on, then press the SETUP BUTTON until the green LED begins to flash. Now, press and hold the PWR SHARE BUTTON. The present value will appear. The display will scroll after three seconds. Hold the button down until 1 appears (see table above). Release the button. The new value will remain in the display for about 5 seconds. When the display reverts to the normal monitoring function the new value is stored in nonvolatile memory.

8