E-10 LINK 2000 DEPOWERED:

Displayed on power up and when power has been interrupted or dipped below theoperatingvoltageoftheLINK2000.Maybecausedbyvoltagedipsduring engine starting if the meter is powered by a starting battery.

E-11 NOT USED:

E-12 BATTERY #1 VOLTAGE SENSE LEADS OPEN:

Check the fuse and connections in the sense lead (Blue wire) to battery #1.

E-13 BATTERY #2 VOLTAGE SENSE LEADS OPEN:

Check the fuse and connections in the sense lead (Violet wire) to battery #2.

E-14 INAPPROPRIATE CHARGED VOLTAGE SELECTED FOR THE SENSED VOLTAGE:

Displayed if the Charged Voltage parameter is above 20 V and sensed voltage is below 20 V, or if the sensed voltage is above 20 V and the Charged Voltage parameter is below 20 V. Helps avoid an erroneous setup. See Charged V.

E-15 INCOMING AC POLARITY REVERSED:

Check incoming AC wiring for a reversed polarity (hot and neutral reversed). See a qualified technician if you do not know how to check for this condition.

CCCINDICATES BATTERY IS BEING CHARGED. Displayed when time remaining is selected.

Exx

CHARGE EFFICIENCY IN DATA DISPLAY

LO BAT

MORE THAN 50% OF DECLARED CAPACITY OF BATTERY #1

 

OR #2 HAS BEEN CONSUMED. SEE PAGE 5.

OL

METER READING OUT OF RANGE.

Pxxx

INDICATES PERCENT OF CHARGE MODE SELECTED.

Uxx

DESIGNATES USER SETUP CEF. SEE F06 PAGE 12.

TO VERIFY CURRENT MEASUREMENT:

 

You may use a digital multimeter to verify that the current measurement is

 

displayed correctly. Place at least a 20- to 30-amp load on the system. Use

 

themultimetertocheckthemillivoltreadingacrossthebatteryshunt.Theshunt

 

has a 500 A 50 mV rating, which means a load of 30 amps generates 3.0 mV

 

across the shunt. The reading at the shunt and at the point where the wires

 

coming out of the meter join the shunt wiring should be the same, and when

 

multipliedby10shouldequalthereadingintheampsdisplayoftheLink2000.

29