York B2CH180 Supply Air Blower Performance, DOWNFLOW DUCT APPLICATIONS m3 /s - B*CH180 UNIT

Models: B2CH180

1 16
Download 16 pages 30.24 Kb
Page 10
Image 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

035-18895-000-A-0902

TABLE 4 - SUPPLY AIR BLOWER PERFORMANCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOWNFLOW DUCT APPLICATIONS (m3 /s) - B*CH180 UNIT

 

 

 

 

 

 

 

 

 

 

 

BLOWER

MOTOR

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

PULLEY

 

1.77 m3/s

 

 

2.07 m3/s

 

 

2.36 m3/s

 

 

2.66 m3/s

 

 

2.95 m3/s

 

SPEED,

(TURNS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ESP

Output

 

Input

ESP

 

Output

 

Input

ESP

 

Output

 

Input

ESP

 

Output

 

Input

ESP

 

Output

 

Input

RPM

 

 

 

 

 

 

 

 

 

OPEN)*

(Pa)

(kW)

 

(kW)

(Pa)

 

(kW)

 

(kW)

(Pa)

 

(kW)

 

(kW)

(Pa)

 

(kW)

 

(kW)

(Pa)

 

(kW)

 

(kW)

 

 

 

 

 

 

 

 

 

 

845

6.0

273

1.56

 

1.8

223

 

1.79

 

2.2

198

 

2.09

 

2.5

174

 

2.38

 

2.9

149

 

2.68

 

3.2

885

5.0

322

1.64

 

1.9

273

 

1.94

 

2.3

223

 

2.24

 

2.7

198

 

2.53

 

3.1

174

 

2.83

 

3.4

925

4.0

372

1.71

 

2.1

322

 

2.01

 

2.5

248

 

2.38

 

2.9

223

 

2.68

 

3.3

-

 

-

 

-

960

3.0

422

1.79

 

2.2

347

 

2.16

 

2.6

298

 

2.46

 

3.0

248

 

2.83

 

3.4

-

 

-

 

-

1000

2.0

446

1.86

 

2.3

397

 

2.24

 

2.7

347

 

2.61

 

3.2

-

 

-

 

-

-

 

-

 

-

1040

1.0

496

1.94

 

2.4

446

 

2.38

 

2.9

372

 

2.76

 

3.3

-

 

-

 

-

-

 

-

 

-

DOWNFLOW DUCT CONNECTIONS (CFM) - B*CH180 UNIT

BLOWER

MOTOR

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

PULLEY

 

3750 CFM

 

 

4380 CFM

 

 

5000 CFM

 

 

5630 CFM

 

 

6250 CFM

 

SPEED,

 

 

 

 

 

 

 

 

 

 

(TURNS

ESP

 

Output

 

Input

ESP

 

Output

 

Input

ESP

 

Output

 

Input

ESP

 

Output

 

Input

ESP

 

Output

 

Input

(RPM)

 

 

 

 

 

 

 

 

 

 

OPEN)*

(iwg)

 

(bhp)

 

(kW)

(iwg)

 

(bhp)

 

(kW)

(iwg)

 

(bhp)

 

(kW)

(iwg)

 

(bhp)

 

(kW)

(iwg)

 

(bhp)

 

(kW)

 

 

 

 

 

 

 

 

 

 

 

845

6.0

1.1

 

2.1

 

1.8

0.9

 

2.4

 

2.2

0.8

 

2.8

 

2.5

0.7

 

3.2

 

2.9

0.6

 

3.6

 

3.2

885

5.0

1.3

 

2.2

 

1.9

1.1

 

2.6

 

2.3

0.9

 

3.0

 

2.7

0.8

 

3.4

 

3.1

0.7

 

3.8

 

3.4

925

4.0

1.5

 

2.3

 

2.1

1.3

 

2.7

 

2.5

1.0

 

3.2

 

2.9

0.9

 

3.6

 

3.3

-

 

-

 

-

960

3.0

1.7

 

2.4

 

2.2

1.4

 

2.9

 

2.6

1.2

 

3.3

 

3.0

1.0

 

3.8

 

3.4

-

 

-

 

-

1000

2.0

1.8

 

2.5

 

2.3

1.6

 

3.0

 

2.7

1.4

 

3.5

 

3.2

-

 

-

 

-

-

 

-

 

-

1040

1.0

2.0

 

2.6

 

2.4

1.8

 

3.2

 

2.9

1.5

 

3.7

 

3.3

-

 

-

 

-

-

 

-

 

-

NOTES: 1. Blower performance includes fixed outdoor air, standard unit filters, a dry indoor coil and no electric heat.

2.Refer to Table 5 for additional static resistances.

ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.

*Do NOT close the pulley below 1 turn open.

10

Unitary Products Group

Page 10
Image 10
York B2CH180 installation instructions Supply Air Blower Performance, DOWNFLOW DUCT APPLICATIONS m3 /s - B*CH180 UNIT

FAQ

What is the ESP in blower performance for York B2CH180 unit?

The External Static Pressure (ESP) available for the supply and return air duct system is provided in the blower performance table.

Are there any specific requirements for using pulleys with York B2CH180 unit?

Do NOT close the pulley below 1 turn open, as per the manufacturer's recommendation.

What factors are considered in the blower performance of York B2CH180 unit?

Blower performance includes fixed outdoor air, standard unit filters, a dry indoor coil and no electric heat. Refer to Table 5 for additional static resistances.