TABLE 4 - SUPPLY AIR BLOWER PERFORMANCE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
DOWNFLOW DUCT APPLICATIONS (m3 /s) - B*CH180 UNIT |
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||
BLOWER | MOTOR |
|
|
|
|
|
|
|
|
|
| AIRFLOW |
|
|
|
|
|
|
|
|
|
|
| ||
PULLEY |
| 1.77 m3/s |
|
| 2.07 m3/s |
|
| 2.36 m3/s |
|
| 2.66 m3/s |
|
| 2.95 m3/s |
| ||||||||||
SPEED, | (TURNS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ESP | Output |
| Input | ESP |
| Output |
| Input | ESP |
| Output |
| Input | ESP |
| Output |
| Input | ESP |
| Output |
| Input | ||
RPM |
|
|
|
|
|
|
|
|
| ||||||||||||||||
OPEN)* | (Pa) | (kW) |
| (kW) | (Pa) |
| (kW) |
| (kW) | (Pa) |
| (kW) |
| (kW) | (Pa) |
| (kW) |
| (kW) | (Pa) |
| (kW) |
| (kW) | |
|
|
|
|
|
|
|
|
|
| ||||||||||||||||
845 | 6.0 | 273 | 1.56 |
| 1.8 | 223 |
| 1.79 |
| 2.2 | 198 |
| 2.09 |
| 2.5 | 174 |
| 2.38 |
| 2.9 | 149 |
| 2.68 |
| 3.2 |
885 | 5.0 | 322 | 1.64 |
| 1.9 | 273 |
| 1.94 |
| 2.3 | 223 |
| 2.24 |
| 2.7 | 198 |
| 2.53 |
| 3.1 | 174 |
| 2.83 |
| 3.4 |
925 | 4.0 | 372 | 1.71 |
| 2.1 | 322 |
| 2.01 |
| 2.5 | 248 |
| 2.38 |
| 2.9 | 223 |
| 2.68 |
| 3.3 | - |
| - |
| - |
960 | 3.0 | 422 | 1.79 |
| 2.2 | 347 |
| 2.16 |
| 2.6 | 298 |
| 2.46 |
| 3.0 | 248 |
| 2.83 |
| 3.4 | - |
| - |
| - |
1000 | 2.0 | 446 | 1.86 |
| 2.3 | 397 |
| 2.24 |
| 2.7 | 347 |
| 2.61 |
| 3.2 | - |
| - |
| - | - |
| - |
| - |
1040 | 1.0 | 496 | 1.94 |
| 2.4 | 446 |
| 2.38 |
| 2.9 | 372 |
| 2.76 |
| 3.3 | - |
| - |
| - | - |
| - |
| - |
DOWNFLOW DUCT CONNECTIONS (CFM) - B*CH180 UNIT
BLOWER | MOTOR |
|
|
|
|
|
|
|
|
|
|
| AIRFLOW |
|
|
|
|
|
|
|
|
|
|
| ||
PULLEY |
| 3750 CFM |
|
| 4380 CFM |
|
| 5000 CFM |
|
| 5630 CFM |
|
| 6250 CFM |
| |||||||||||
SPEED, |
|
|
|
|
|
|
|
|
|
| ||||||||||||||||
(TURNS | ESP |
| Output |
| Input | ESP |
| Output |
| Input | ESP |
| Output |
| Input | ESP |
| Output |
| Input | ESP |
| Output |
| Input | |
(RPM) |
|
|
|
|
|
|
|
|
|
| ||||||||||||||||
OPEN)* | (iwg) |
| (bhp) |
| (kW) | (iwg) |
| (bhp) |
| (kW) | (iwg) |
| (bhp) |
| (kW) | (iwg) |
| (bhp) |
| (kW) | (iwg) |
| (bhp) |
| (kW) | |
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||
845 | 6.0 | 1.1 |
| 2.1 |
| 1.8 | 0.9 |
| 2.4 |
| 2.2 | 0.8 |
| 2.8 |
| 2.5 | 0.7 |
| 3.2 |
| 2.9 | 0.6 |
| 3.6 |
| 3.2 |
885 | 5.0 | 1.3 |
| 2.2 |
| 1.9 | 1.1 |
| 2.6 |
| 2.3 | 0.9 |
| 3.0 |
| 2.7 | 0.8 |
| 3.4 |
| 3.1 | 0.7 |
| 3.8 |
| 3.4 |
925 | 4.0 | 1.5 |
| 2.3 |
| 2.1 | 1.3 |
| 2.7 |
| 2.5 | 1.0 |
| 3.2 |
| 2.9 | 0.9 |
| 3.6 |
| 3.3 | - |
| - |
| - |
960 | 3.0 | 1.7 |
| 2.4 |
| 2.2 | 1.4 |
| 2.9 |
| 2.6 | 1.2 |
| 3.3 |
| 3.0 | 1.0 |
| 3.8 |
| 3.4 | - |
| - |
| - |
1000 | 2.0 | 1.8 |
| 2.5 |
| 2.3 | 1.6 |
| 3.0 |
| 2.7 | 1.4 |
| 3.5 |
| 3.2 | - |
| - |
| - | - |
| - |
| - |
1040 | 1.0 | 2.0 |
| 2.6 |
| 2.4 | 1.8 |
| 3.2 |
| 2.9 | 1.5 |
| 3.7 |
| 3.3 | - |
| - |
| - | - |
| - |
| - |
NOTES: 1. Blower performance includes fixed outdoor air, standard unit filters, a dry indoor coil and no electric heat.
2.Refer to Table 5 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.
*Do NOT close the pulley below 1 turn open.
10 | Unitary Products Group |