OPTIONAL ECONOMIZER / MOTORIZED DAMPER RAIN HOOD

These heaters are located within the central compartment of the unit with the heater elements extending into the supply air chamber. Refer to Figure 7 for access panel location.

Fuses are supplied, where required, by the factory. Some KW sizes require fuses and others do not. Refer to Table 2 for minimum air flow limitations and to Table 8 for electrical data.

OPTIONAL ECONOMIZER / MOTORIZED DAMPER RAIN HOOD

The instructions for the optional economizer / motorized damper rain hood can be found in form 44-320-2. The procedures listed in those instructions should be used when field assembling an economizer rain hood onto a unit. The outdoor and return air dampers, the damper actuator, the damper linkage, the outdoor and return air divider baffles, and all the control sensors are factory mounted as part of the “factory installed” economizer option.

ENTHALPY SETPOINT ADJUSTMENT

Remove the economizer access panel from the unit to check the following adjustments. Loosen but do not remove the two panel latches.

035-18895-000-A-0902

CAUTION: Extreme care must be exercised in turning both the setpoint and minimum position adjusting screws to prevent twisting them off.

1.The enthapy set point for the dampers may now be set by selecting the desired setpoint shown in Figure 6. Adjust as follows:

For single enthalpy operation, carefully turn the setpoint adjusting screw to the “A”, “B”, “C” or “D” setting corre- sponding to the lettered curve.

For dual enthapy operation, carefully turn the setpoint adjusting screw fully clockwise past the “D” setting.

2.To check that the damper blades move smoothly without binding, carefully turn the minimum postion adjusting screw fully clockwise and then energize and de-energize termi- nals “R” to “G”. With terminals “R” to “G” energized, turn the minimum position screw counterclockwise until the desired minimum position has been attained.

3.Replace the economizer access panel. Reposition the two latches horizontally and retighten the screws.

6

Unitary Products Group

Page 6
Image 6
York B2CH180 installation instructions Optional Economizer / Motorized Damper Rain Hood

FAQ

What is the purpose of the optional economizer and motorized damper rain hood?

The optional economizer and motorized damper rain hood helps to regulate air flow and protect the unit from rain and other weather elements.

How do I adjust the enthalpy setpoint?

To adjust the enthalpy setpoint, carefully turn the setpoint adjusting screw to the desired setting as shown in Figure 6 of the manual.

Do I need fuses for all KW sizes of the York B2CH180 heat pump?

Fuses are supplied by the factory where required. Refer to Table 2 for minimum air flow limitations and to Table 8 for electrical data to determine if fuses are needed for specific KW sizes.