York B2CH180 Typical Field Wiring, Power And Control Wiring, Optional Electric Heaters

Models: B2CH180

1 16
Download 16 pages 30.24 Kb
Page 5
Image 5
FIG. 5 - TYPICAL FIELD WIRING

035-18895-000-A-0902

POWER WIRING

￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿

￿￿￿￿￿

￿￿￿￿￿

￿￿￿￿￿

￿￿￿￿￿￿

FIG. 5 - TYPICAL FIELD WIRING

insulated wires 1.0mm2 (#18 AWG) should be used to connect thermostat to unit. Eight conductors are required.

The subbase on the low voltage thermostat includes an “Emergency Heat ” position on the system switch and a pilot light. In the “Emergency Heat” position, the thermostat provides electric resistance heat only. The compressors will not run. The pilot light indicates that the switch is on “EM HT”. Nine conductors are required for this application.

POWER AND CONTROL WIRING

Field wiring to the unit and electrical grounding of the unit must conform to the applicable national, and local or municipal codes. Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 1.

The internal wiring harness furnished in this unit is an integral part of the unit. Field alteration to comply with electrical codes should not be required.

A fused disconnect switch should be field provided for the unit. The switch must be separate from all other circuits. Refer to Figure 7 for installation location. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram. Refer to Table 7 for electrical data.

Electrical line must be sized correctly to carry the load. USE COPPER CONDUCTORS ONLY. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.

CAUTION: When connecting electrical power and control wir- ing to the unit, waterproof type connectors MUST

BE USED so that water or moisture cannot be drawn into the unit during normal operation. The above waterproofing conditions will also apply when installing a field-supplied disconnect switch.

Refer to Figure 5 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information.

OPTIONAL ELECTRIC HEATERS

The factory installed heaters are wired for single point power supply. Power supply need only be brought into the single point terminal block and thermostat wiring to the low voltage terminal strip located in the upper portion of the unit control box.

TABLE 2 - ELECTRIC HEAT APPLICATION DATA

 

Minimum

Output by Operation Mode and

 

 

Heat Stage

 

Heater

Airflow

 

 

 

kW @ 400/415V*

 

Model

m3/s (CFM)

 

 

Normal Operation

Emergency Heat

 

 

 

180

W1

W2

W1

W2

E018

2.12

Mechanical

11.3/13.5

11.3/13.5

None

(4500)

 

 

 

 

 

E036

2.12

Mechanical

11.3/13.5

11.3/13.5

11.3/13.5

(4500)

 

 

 

 

 

E054

2.36

Mechanical

11.3/13.5

11.3/13.5

22.6/26.9

(5000)

 

 

 

 

 

E072

2.36

Mechanical

22.6/26.9

22.6/26.9

22.6/26.9

(5000)

 

 

 

 

 

*Refer to Table 8 for total heater output kW for the respective heater.

Unitary Products Group

5

Page 5
Image 5
York B2CH180 Typical Field Wiring, Power And Control Wiring, Optional Electric Heaters, Electric Heat Application Data

FAQ

What type of wires should be used to connect the thermostat to the unit?

Insulated wires 1.0mm2 #18 AWG should be used to connect thermostat to unit.

How many conductors are required for the Emergency Heat position on the thermostat?

Eight conductors are required for the Emergency Heat position on the thermostat.

What type of connectors should be used when connecting electrical power and control wiring to the unit?

Waterproof type connectors MUST BE USED to prevent water or moisture from being drawn into the unit during normal operation.