York D2EE 036, D1EE 048, D1EE 060 Static Resistances, MOTOR AND DRIVE DATA - Belt-DriveBlower

Models: D2EE 036 D1EE 060 D1EE 048

1 16
Download 16 pages 8.1 Kb
Page 11
Image 11
TABLE 6 - STATIC RESISTANCES

035-12046-003-A-0204

TABLE 6 - STATIC RESISTANCES

EXTERNAL STATIC PRESSURE DROP

 

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

DESCRIPTION

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

Economizer1, 3

 

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.30

Electric Heaters1

 

5 - 15 KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.22

 

20 - 30 KW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

 

 

Bottom Duct Connections1

 

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

0.19

0.22

Cooling Only2

 

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.23

0.26

0.29

0.32

1Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2Add these resistance values to the available static resistance in the respective Blower Performance Table.

3The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 7 - MOTOR AND DRIVE DATA - Belt-Drive Blower

 

 

 

 

MOTOR*

 

ADJUSTABLE

 

FIXED

BELT

 

BLOWER

 

 

 

MOTOR PULLEY

BLOWER PULLEY

 

 

 

 

 

 

 

 

MODEL

RANGE

 

 

 

FRAME

SERVICE

PITCH

BORE

PITCH

BORE

PITCH

DESIG-

 

(RPM)

HP

RPM

 

DIA.

DIA.

 

LENGTH

 

 

SIZE

FACTOR

(in.)

 

(in.)

NATION

 

 

 

 

 

(in.)

(in.)

 

(in.)

 

 

 

 

 

 

 

 

 

 

 

DEE036

790 - 1120

1-1/2

1725

 

56

1.15

2.4 - 3.4

7/8

5.7

 

1

37.3

A36

DEE048

790 - 1120

1-1/2

1725

 

56

1.15

2.4 - 3.4

7/8

5.7

 

1

37.3

A36

DEE060

850 - 1220

1-1/2

1725

 

56

1.15

2.4 - 3.4

7/8

5.2

 

1

37.3

A36

*All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device.

TABLE 8 - ELECTRICAL DATA - Units w/Direct-Drive Blower Motor

 

 

VOLTAGE

 

 

COND.

 

SUPPLY

TOTAL

MAX.

MAX.

 

 

LIMITATIONS

COMPRESSOR

 

AIR

FUSE

HACR

MODEL

POWER SUP-

FAN

 

UNIT

(SEE NOTE 1)

 

 

 

BLOWER

SIZE,

BREAKER

DEE

PLY

 

 

MOTOR,

 

AMPACITY,

MIN.

MAX.

RLA

LRA

 

MOTOR,

(SEE NOTE 2)

SIZE,

 

 

FLA

 

FLA

AMPS

AMPS

AMPS

 

208/230-1-60

187

253

16.7

87

2.3

 

4.4

27.5

40

40

036

208/230-3-60

187

253

13.1

110

2.3

 

4.4

23.1

35

35

460-3-60

414

504

6.7

54

1.4

 

2.2

12.0

15

15

 

 

 

575-3-60

518

630

5.1

44

1.4

 

2.2

10.7

15

 

208/230-1-60

187

253

18.7

135

2.3

 

5.0

38.6

60

60

048

208/230-3-60

187

253

11.9

130

2.3

 

5.0

25.7

40

40

460-3-60

414

504

6.3

64.0

1.4

 

2.2

13.2

20

20

 

 

 

575-3-60

518

630

4.9

52.0

1.4

 

2.2

11.4

15

 

208/230-1-60

187

253

32.1

169

2.3

 

6.6

49.0

80

80

060

208/230-3-60

187

253

19.3

123

2.3

 

6.6

33.0

50

50

460-3-60

414

504

10.0

62

1.4

 

3.3

17.2

25

25

 

 

 

575-3-60

518

630

7.9

50

1.4

 

3.3

14.6

20

NOTES: 1. Utilization Range “A” in accordance with ARI Standard 110.

2. Dual element, time delay type.

 

 

 

 

TABLE 9 - ELECTRICAL DATA - Units w/Belt-Drive Blower Motor

 

 

VOLTAGE

 

 

COND.

 

SUPPLY

TOTAL

MAX.

MAX.

 

POWER SUP-

LIMITATIONS

COMPRESSOR

 

AIR

FUSE

HACR

MODEL

FAN

 

UNIT

(SEE NOTE 1)

 

 

 

BLOWER

SIZE,

BREAKER

DEE

PLY

 

 

MOTOR,

 

AMPACITY,

 

 

 

 

 

MOTOR,

(SEE NOTE 2)

SIZE,

 

 

MIN.

MAX.

RLA

LRA

FLA

 

AMPS

 

 

 

FLA

AMPS

AMPS

 

 

 

 

 

 

 

 

 

 

208/230-1-60

187

253

16.7

87

2.3

 

7.6

30.7

45

45

036

208/230-3-60

187

253

13.1

110

2.3

 

5.3

23.9

35

35

460-3-60

414

504

6.7

54

1.4

 

2.6

12.4

20

20

 

 

 

575-3-60

518

630

5.1

44

1.4

 

2.0

9.8

15

15

 

208/230-1-60

187

253

18.7

135

2.3

 

8.6

42.6

60

60

048

208/230-3-60

187

253

11.9

130

2.3

 

5.2

26.3

40

40

460-3-60

414

504

6.3

64.0

1.4

 

2.6

14.3

20

20

 

 

 

575-3-60

518

630

4.9

52.0

1.4

 

2.0

11.4

15

15

 

208/230-1-60

187

253

32.1

169

2.3

 

8.6

51.0

80

80

060

208/230-3-60

187

253

19.3

123

2.3

 

6.0

32.4

50

50

460-3-60

414

504

10.0

62

1.4

 

3.0

16.9

25

25

 

 

 

575-3-60

518

630

7.9

50

1.4

 

2.4

13.7

20

20

NOTES: 1. Utilization Range “A” in accordance with ARI Standard 110.

2. Dual element, time delay type.

 

 

 

 