035-12046-003-A-0204

OPERATION

The heaters are wired for a single point power supply. Power supply need only be brought into the single point terminal block and thermostat wiring to the low voltage terminal strip located in the upper portion of the unit control box.

Fuses are supplied, where required, by the factory. Some KW sizes require fuses and others do not. Refer to the accessory instruction for electrical data.

COOLING SYSTEM

The cooling section is a complete factory package utilizing an air-cooled condenser. The system is factory-charged with Refrigerant-22. The compressor is hermetically sealed and internally sprung.

The compressors have inherent (internal) protection. If there is an abnormal temperature rise in the compressor, the protector will open to shut down the compressor.

PRELIMINARY OPERATION COOLING

After the installation has been completed, the crankcase heater of the compressor must be energized for at least 4 hours before starting the unit. After this initial warm-up, the compressor should be given three false starts (energized just long enough to make a few revolutions) with a 5 minute delay between each start before being put into full time service.

NOTE: Prior to each cooling season, the crankcase heater must be energized at least 10 hours before the system is put into operation.

COOLING SEQUENCE OF OPERATION

Single-Stage Cooling:

When the thermostat calls for “cooling”, “R” is closed to “G” and “Y1" (wiring schematic) which completes the low voltage control circuit, immediately energizing the compressors, condenser fan motor and blower motor simultaneously.

Two-Stage Cooling:

A two-stage cooling thermostat may be used if the unit has an economizer. First-stage cooling is provided by the economizer if the outdoor air enthalpy is acceptable, and second-stage cooling is provided by the compressor. Jumper wire J1 must be removed. Refer to unit wiring diagram.

After the thermostat is satisfied and opens, the blower will continue to run for a short time. All other components will stop.

SAFETY CONTROLS

The refrigerant system is equipped with the following safety controls:

1.A Suction Line Freezestat to protect against low evaporator temperatures due to a low air flow or a low return air tem- perature.

2.A High Pressure Cutout Switch to protect against excessive discharge pressures due to a blocked condenser coil or a condenser motor failure.

3.A Low Pressure/Loss of Charge

Switch to protect against loss of refrigerant charge.

If either of the above safety controls opens, the refrigerant system will be locked out. The lock out of the system can be

reset by opening the 24V circuit either at the room thermostat or at the unit disconnect.

HEATING SEQUENCE OF OPERATION

The following sequence of operation is based on using a standard single-stage or two-stage heating thermostat.

WITH POWER TO UNIT AND THERMOSTAT IN THE HEATING MODE

Single-Stage Heating:

a.If the fan switch is in the “ON” position, the evaporator blower motor relay (BR) will be energized through terminal G to provide continuous blower operation. If the fan switch is in the “AUTO” position, the blower will operate only when there is a call for heating by the thermostat.

b.Upon a call for heat by the thermostat, the first stage of heat will be energized. Sequencer 1S (or contactor 2M) is al- ways the first and last to complete its timing cycle and con- trols power to the evaporator blower motor.

c.The thermostat will cycle the electric heat to satisfy the heating requirements of the conditioned space.

Two-Stage Heating:

a.If the fan switch is in the “ON” position, the evaporator blower motor relay (BR) will be energized through terminal G to provide continuous blower operation. If the fan switch is in the “AUTO” position, the blower will operate only when there is a call for heating by the thermostat.

b.Upon a call for first-stage heat by the thermostat, the first stage of heat will be energized.

If the thermostat calls for the second stage of heat, the second stage of heat will be energized.

As before, sequencer 1S (or contactor 2M) maintains control of the evaporator blower.

c.The thermostat will cycle the electric heat to satisfy the heating requirements of the conditioned space.

CONTINUOUS BLOWER - Continuous blower operation is possible by closing the R to G circuit on the thermostat.

TABLE 10 - HEAT ANTICIPATOR SETTING

NOMINAL

 

SETTING, AMPS

HEATER

VOLTAGE

 

 

SIZE

TH1

TH2

 

KW

 

 

 

5

 

0.16

-

7

 

0.35

-

10

240-1-60

0.35

-

15

0.35

0.19

 

20

 

0.35

0.38

30

 

0.35

0.38

5

 

0.35

-

7

 

0.35

-

10

240-3-60

0.35

-

15

0.35

0.19

 

20

 

0.35

0.38

30

 

0.35

0.38

7

 

0.35

-

10

 

0.35

-

15

480-3-60

0.35

-

20

 

0.37

0.29

30

 

0.37

0.29

10

 

0.35

-

15

600-3-60

0.35

-

20

0.37

0.29

 

30

 

0.37

0.29

12

Unitary Products Group

Page 12
Image 12
York D1EE 048, D1EE 060, D2EE 036 installation instructions Operation

D2EE 036, D1EE 060, D1EE 048 specifications

The York D1EE 048, D2EE 036, and D1EE 060 are advanced air conditioning units designed for superior performance and energy efficiency in commercial and industrial environments. These models are part of York’s reputation for creating reliable HVAC systems that cater to a variety of applications.

The York D1EE 048 is a high-efficiency rooftop unit, renowned for its compact design and robust construction. This model boasts an integrated economizer that enhances energy savings by optimizing the use of outside air for cooling. It features a cutting-edge variable speed compressor, which provides precision cooling and reduces energy consumption under varying load conditions. The advanced microprocessor control system enables quick adjustments to system performance, further enhancing comfort and efficiency.

In contrast, the York D2EE 036 is another exemplary model, distinguished by its dual-stage heating and cooling capabilities. This unit is particularly advantageous for facilities requiring consistent temperature control throughout different seasons. With a SEER rating that meets or exceeds regulatory requirements, the D2EE 036 helps operators minimize downtime and achieve lower operational costs. Its innovative design includes a streamlined airflow system, enabling quiet operation without compromising cooling performance.

Finally, the York D1EE 060 rounds out this trio with its innovative features tailored for large-building applications. This unit is equipped with advanced inverter technology, which allows for seamless adjustments in cooling capacity based on real-time demand. The unit is designed with high-performance heat exchangers that optimize thermal transfer efficiency, ensuring rapid cooling response while maintaining low energy usage. Its smart connectivity features allow for remote monitoring and adjustments, offering facility managers enhanced control over the indoor climate.

In terms of characteristics, all three models prioritize energy efficiency, user-friendly controls, and environmentally responsible refrigerants. They comply with the latest energy standards, making them suitable for organizations aiming for sustainability. With their robust construction and user-centric features, York’s D1EE 048, D2EE 036, and D1EE 060 units represent a commitment to delivering efficient, reliable, and cutting-edge climate control solutions. Whether for small offices or large industrial spaces, these systems provide an optimal balance of performance and cost-effectiveness.