York D1EE 060, D1EE 048 Condensate Drain, Service Access, Power And Control Wiring, Thermostat

Models: D2EE 036 D1EE 060 D1EE 048

1 16
Download 16 pages 8.1 Kb
Page 4
Image 4
CONDENSATE DRAIN

kept clean or replaced with same size and type. Dirty filters will reduce the capacity of the unit and will result in frosted coils or safety shutdown. Minimum filter area and required sizes are shown in Table 2.

CONDENSATE DRAIN

Plumbing must conform to local codes. Use a sealing

FIG. 2 - RECOMMENDED DRAIN PIPING

compound on male pipe threads. Install a condensate drain line from the 3/4" PVC female connection on the unit to spill into an open drain.

NOTE: The condensate drain line MUST be trapped to pro- vide proper drainage. See Figure 2.

SERVICE ACCESS

Access to all serviceable components is provided by the following removable panels:

Compressor compartment

Heater compartment

Blower compartment

Main control box

Filter compartment

Motor Access (on units w/belt-drive option)

Refer to Figure 5 for location of these access panels.

CAUTION: Make sure that all screws are replaced on the unit to maintain an air-tight seal.

035-12046-003-A-0204

NOTE: If the unit has an economizer, remove jumper J1 from terminals 8 and 10 on the relay board to prevent simul- taneous operation of the compressor and the econo- mizer. If you want to control the economizer on a second stage of cooling, use a thermostat with two stages of cooling.

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of the National Electrical Code (NEC) ANSI/NFPA70 (in USA), current Canadian Electric Code (CEC) C22.1 (in Canada) and/or local ordinances. The unit must be electrically grounded in accordance with the NEC and CEC (as specified above) and/or local codes. Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 1.

The wiring harness furnished with this unit is an integral part of a UL design certified unit. Field alteration to comply with electrical codes should not be required.

A disconnect switch should be field provided for the unit. The switch must be separate from all other circuits. Refer to Figure 5 for installation location. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram.

Electrical lines must be sized properly to carry the load. USE COPPER CONDUCTORS ONLY. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly protected.

CAUTION: When connecting electrical power and control wir- ing to the unit, waterproof type connectors MUST BE USED so that water or moisture cannot be drawn into the unit during normal operation. The above waterproofing conditions will also apply when installing a field-supplied disconnect switch.

Refer to Figure 4 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information.

THERMOSTAT

The room thermostat should be located on an inside wall approximately 56" above the floor where it will not be subject to drafts, sun exposure, or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with thermostat for general installation procedure. Color coded insulated wires (#18 AWG) should be used to connect thermostat to unit. See Figure 4 for wiring details.

TABLE 2 - PHYSICAL DATA

BLOWER SPEED SELECTION

Three blower motor speeds are available on the direct-drive units. The speed selection for the direct-drive units is determined by the CFM and ESP requirements of the applications. All units with belt-drive option have an adjustable motor pulley to achieve the above conditions.

All direct-drive units with 208/230 voltage are shipped with the wire labeled #116 connected to the “HIGH” speed tap on the blower motor. If a lower blower motor speed is desired, this wire should be moved to the “MED” or “LOW” speed tap on the

motor for the speed desired.

 

MODELS

 

DEE

 

 

036

048

060

 

 

EVAPORATOR

CENTRIFUGAL BLOWER (Dia. x Wd. in.)

12 x￿￿10

12 ￿x￿10

12 x 10

FAN MOTOR HP (Direct-Drive)

 

 

1

BLOWER

 

 

FAN MOTOR HP (Belt-Drive)

1.5

1.5

1.5

 

EVAPORATOR

ROWS DEEP

3

3

3

FINS PER INCH

13

13

13

COIL

FACE AREA (Sq. Ft.)

3.6

4.3

5.1

 

CONDENSER

PROPELLER DIA. (in.)

22￿￿

22￿￿

22￿￿

FAN MOTOR HP

 

 

 

FAN

 

 

 

NOM. CFM TOTAL

4,500

4,200

4,500

 

CONDENSER

ROWS DEEP

2

2

2

FINS PER INCH

18

18

18

COIL

FACE AREA (Sq. Ft.)

17.1

17.1

17.1

 

AIR

QUANTITY PER UNIT (15" x 20" x 1")

2

2

2

FILTERS

QUANTITY PER UNIT (14" X 25" X 1")

1

1

1

(SEE NOTE)

TOTAL FACE AREA (sq. ft.)

6.6

6.6

6.6

CHARGE

REFRIGERANT 22 (lbs./oz.)

9/12

9/8

9/8

COMPRESSOR

QUANTITY PER UNIT (HERMETIC TYPE)

1/RECPT

1/RECPT

1/SCROLL

NOTE: Filter racks are adapted for 1" or 2" thick filters.

WEIGHTS (LBS)

 

3 Ton

545

Basic Unit

4 Ton

585

 

5 Ton

610

ACCESSORIES / OPTIONS

Electric Heat

5 - 7 KW

18

10 - 15 KW

23

(Nominal KW)

20 - 30 KW

28

 

Economizer

 

50

Motorized Outdoor

26

Air Damper

 

 

 

Relief/Fixed

 

10

Air Damper

 

 

 

Roof Mounting Curb

92

Belt-Drive Blower

5

4

Unitary Products Group

Page 4
Image 4
York D1EE 060, D1EE 048 Condensate Drain, Service Access, Power And Control Wiring, Thermostat, Blower Speed Selection