254892-YTG-C-0606

PHYSICAL AND ELECTRICAL DATA - 1 PHASE

MODEL

 

H2RD018S06

H2RD024S06

H2RD030S06

H2RD036S06

H2RD042S06

H2RD048S06

H2RD060S06

Unit Supply Voltage

 

 

 

208-230V, 1φ, 60Hz

 

 

 

 

 

 

 

 

 

 

 

Normal Voltage Range 1

 

 

 

 

187 to 252

 

 

 

Minimum Circuit Ampacity

9.4

11.8

15.1

 

18.3

18.3

30.3

32.7

 

 

 

 

 

 

 

 

 

Max. Overcurrent Device Amps 2

15

20

25

 

30

30

50

50

Min. Overcurrent Device Amps 3

15

15

20

 

20

20

35

35

Compressor Type 4

Recip

Recip

Recip

 

Recip

Recip

Scroll B

Scroll B

Compressor

 

Rated Load

6.4

9.0

10.7

 

13.4

13.5

23.0

25.0

Amps

 

Locked Rotor

36

48

61

 

78

78

115

150

 

 

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

No

No

No

 

No

No

No

No

 

 

 

 

 

 

 

 

 

 

Fan Motor Amps

 

Rated Load

0.8

0.5

1.5

 

1.5

1.5

1.5

1.5

 

 

 

 

 

 

 

 

 

 

Fan Diameter Inches

18

22

22

 

22

22

24

24

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated HP

1/8

1/15

1/4

 

1/4

1/4

1/4

1/4

Fan Motor

 

 

 

 

 

 

 

 

 

 

 

Nominal RPM

1075

850

850

 

850

850

850

850

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal CFM

2150

2,200

3100

 

3150

3550

3550

3600

 

 

 

 

 

 

 

 

 

 

 

 

 

Face Area Sq. Ft.

11.43

15.72

15.72

 

15.72

23.60

24.00

27.00

Coil

 

 

 

 

 

 

 

 

 

 

 

Rows Deep

1

1

1

 

1

1

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

Fin / Inches

22

18

22

 

22

22

22

22

 

 

 

 

 

 

 

 

 

 

Liquid Line OD (Field Installed)

3/8

3/8

3/8

 

3/8

3/8

3/8

3/8

 

 

 

 

 

 

 

 

 

Vapor Line OD (Field Installed)

3/4

3/4

3/4

 

7/8

7/8

7/8

1-1/8

 

 

 

 

 

 

 

 

 

Unit Charge (Lbs. - Oz.) 5

4 - 9

5 - 8

5 - 13

 

6 - 0

8 - 13

8 - 6

10 - 2

Charge Per Foot, Oz.

0.68

0.68

0.70

 

0.70

0.70

0.70

0.76

 

 

 

 

 

 

 

 

 

Operating Weight Lbs.

151

151

183

 

183

193

215

220

 

 

 

 

 

 

 

 

 

 

 

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.

4.All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.

5.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon

Crequest.

DIMENSIONS

 

Unit

Dimensions

Refrigerant Connection

 

Model

 

(Inches)

 

Service Valve Size

A

 

A1

B

C

Liquid

Vapor

 

 

 

018

23

35

23

 

 

 

024

27

37

27

 

3/4”

 

030

27

37

27

 

 

B

036

27

37

27

3/8”

 

042

39

37

27

 

7/8”

 

 

 

048

34

43

32

 

 

 

060

38

43

32

 

7/8”*

 

1.

Including Fan Guard.

 

 

 

* Adapter fitting required for 1-1/8” line set.

 

2

Unitary Products Group

Page 2
Image 2
York H*RD036 THRU 060, H*RD018 THRU 060 warranty Physical and Electrical Data 1 Phase, Dimensions, Model, Unit