York H*RD036 THRU 060, H*RD018 THRU 060 warranty YTG-C-0606

Models: H*RD018 THRU 060 H*RD036 THRU 060

1 24
Download 24 pages 57.37 Kb
Page 8
Image 8
Manual background

254892-YTG-C-0606

Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 Phase (Continued)

Outdoor Unit

H1RD030S(25,46)

H1RD036S(25,46)

 

H1RD042S(25,46)

 

H1RD048S(25,46)

H1RD060S(25,46)

Required TXV

1TVM2A1

1TVM2A1

 

1TVM2C1

 

1TVM2C1

1TVM2C1

Factory R-22 Charge, lbs-oz

5 - 13

6 - 0

 

8 - 13

 

8 - 6

10 - 2

 

 

 

 

 

 

 

 

Indoor Coil1

 

 

Additional Charge, Oz

 

 

G4FA036S14T2A

0

 

 

G4FA048S17T2A

0

 

 

G4FA048S17T2C

 

0

 

G4FA048S21T2A

0

 

 

G4FA048S21T2C

 

0

 

G4FA060S21T2C

 

 

0

G4FA060S24T2C

 

 

0

G4FD036H17T2A

0

0

 

 

G4FD036H21T2A

0

 

 

G4FD042H21T2A

0

 

 

G4FD042H21T2C

 

0

 

G4FD046H17T2A

0

 

 

G4FD046H17T2C

 

0

 

G4FD048H21T2C

 

0

 

0

G4FD048H24T2C

 

0

 

0

G4FD060H24T2C

 

 

0

G4FD061H24T2C

 

 

0

F4FP040H06T2A

0

 

 

F4FP042H06T2A

0

 

 

F2FP048H06T2C

 

0

 

FOOTNOTES:

 

 

 

 

 

 

 

1.Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.

PROCEDURES:

1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of inter- connecting

line tubing.

2.Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.

3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.

4.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.

8

Unitary Products Group

Page 8
Image 8
York H*RD036 THRU 060, H*RD018 THRU 060 warranty YTG-C-0606