■ Electrical Work
Model | Power Source | Switch and | Wiring size | ||
Fuse rating | |||||
|
|
|
| ||
10A | f 1.0 mm2 | ||||
|
| ||||
|
|
| |||
|
|
|
| ||
12000 Btu/h | 16A | f 1.5 mm2 | |||
|
| ||||
|
|
| |||
|
|
|
|
| |
18000 Btu/h | ~ 50Hz | 25A |
| ||
|
|
| |||
~ 60Hz | f 2.5 mm2 | ||||
|
| ||||
24000 Btu/h | ~ 50Hz | 32A | |||
| |||||
|
|
| |||
~ 60Hz |
| ||||
|
|
| |||
|
|
|
|
|
NOTE
The supply volyage must be consistent with the rate voltage of the air conditioner.
■Defrosting operation (Available for heating only)
1.Condition to start defrosting: Units will switch to defrosting mode when either of the following conditions is met.
a.Unit has been running under T3<0ºC for 40 minutes and
T3 (°C) | Starting Defrosting Mode under condition a. |
|
2 |
|
|
|
|
|
| Time |
|
|
|
|
|
| Elapsed | |
|
|
|
|
|
| (min) | |
|
|
|
|
|
|
| |
110023 | 5 | 10 | 15 | 20 | 253035 | 403 min45 | 50 |
4 |
|
| 40 min |
|
|
| |
|
|
| Heating mode | Defrosting mode | |||
|
|
|
|
|
|
|
b. Unit has been running at high temperature protection mode* for 90 minute. (*High temperature protection mode: when coil temperature of indoor unit reaches 55°C, outdoor unit will turn off external unit fan but still keep compressor running).
2.Condition to stop defrosting: Units will switch back to heating mode when either of the following conditions is met.
a.Unit has been running at defrosting mode for 10 minutes.
b.T3>20 ºC
Remark: T3 is coil temperature of outdoor units.