![Table 7: Natural Gas Pipe Sizing Chart1](/images/new-backgrounds/35090/3509031x1.webp)
Table 7: Natural Gas Pipe Sizing Chart1
Length |
| Nominal Inches Iron Pipe Size |
| |||
In Feet | 1/2” |
| 3/4” | 1” |
| |
10 | 132 |
| 278 | 520 |
| 1,050 |
20 | 92 |
| 190 | 350 |
| 730 |
30 | 73 |
| 152 | 285 |
| 590 |
40 | 63 |
| 130 | 245 |
| 500 |
50 | 56 |
| 115 | 215 |
| 440 |
60 | 50 |
| 105 | 195 |
| 400 |
70 | 46 |
| 96 | 180 |
| 370 |
80 | 43 |
| 90 | 170 |
| 350 |
90 | 40 |
| 84 | 160 |
| 320 |
100 | 38 |
| 79 | 150 |
| 305 |
1.Maximum capacity of pipe in cubic feet of gas per hour (based upon a pressure drop of 0.3 inch water column and 0.6 specific gravity gas).
Table 8: Propane (LP) Gas Pipe Sizing Chart1
Length |
| Nominal Inches Iron Pipe Size |
| |||
In Feet | 1/2” |
| 3/4” | 1” |
| |
10 | 275 |
| 567 | 1,071 |
| 2,205 |
20 | 189 |
| 393 | 732 |
| 1,496 |
30 | 152 |
| 315 | 590 |
| 1,212 |
40 | 129 |
| 267 | 504 |
| 1,039 |
50 | 114 |
| 237 | 448 |
| 913 |
60 | 103 |
| 217 | 409 |
| 834 |
70 | 96 |
| 196 | 378 |
| 771 |
80 | 89 |
| 185 | 346 |
| 724 |
90 | 83 |
| 173 | 322 |
| 677 |
100 | 78 |
| 162 | 307 |
| 630 |
1.Maximum capacity of pipe in thousands of BTU per hour (based upon a pressure drop of 0.5 inch water column).
If flexible stainless steel tubing is allowed by the authority having jurisdiction, wrought iron or steel pipe must be installed at the gas valve and extend a minimum of two (2) inches outside of the unit casing.
Natural gas may contain some propane. Propane being an excellent solvent, will quickly dissolve white lead or most standard commercial compounds. Therefore, a special pipe dope must be applied when wrought iron or steel pipe is used. Shellac base compounds such as gaskoloc or stalastic, and compounds such as rectorseal # 5, Clyde’s or John Crane may be used.
4.All piping should be cleaned of dirt and scale by hammering on the outside of the pipe and blowing out the loose dirt and scale. Before initial
5.The gas supply should be a separate line and installed in accordance with all safety codes as prescribed under
Limitations, shown on Page 3. After the gas connections have been completed, open the main
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could result in serious injury, death or property damage.
Never test for gas leaks with an open flame. use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
6.The furnace must be isolated from the gas supply piping system by closing its individual manual
Flue Vent Hood
The flue vent hood with screen is shipped loose. This hood must be installed to assure proper unit operation. The hood must be fastened to the outside of the side gas control/electrical compartment with the screws provided in the bag attached to the inside of the gas control/electrical compartment, see Figure 13.
Flue hood surfaces may be hot.
9(17287/(76&5((1
)/8(9(17287/(7 $,5+22'
Figure 13: Flue Vent Outlet Air Hood
The flue exhaust hood must be properly installed and within the recommended clearances. Further commu- nications and action must be given to the home or building owner(s) to eliminate any unauthorized human contact around this area during the heating cycle. Flue hood surface and the immediate area reach high tem- peratures during the heating cycle.
16 | Unitary Products Group |