York R-410A dimensions Start-Up, Circulating Fan, Prestart Check List, Operating Instructions

Models: R-410A

1 36
Download 36 pages 24.83 Kb
Page 25
Image 25
Circulating Fan

279550-YIM-A-0207

Circulating Fan

When the thermostat calls for FAN, the thermostat terminal G is energized signaling the circulating fan to run at the heat speed 2 seconds after the G terminal is energized.

If a call for HEAT occurs, the circulating fan continues to run at the heat speed.

If a call for COOL occurs, the circulating fan switches to cool speed according to the fan delay profile selected in Table 17.

When the thermostat ends the call for FAN, the thermostat terminal G is de-energized, de-energizing the circulating fan.

Start-Up

Prestart Check List

Complete the following checks before starting the unit.

1.Check the type of gas being supplied. Be sure that it is the same as listed on the unit nameplate.

2.Make sure that the vent outlet air hood has been properly installed.

Operating Instructions

1.STOP! Read the information on the unit safety label.

2.Set the thermostat to the OFF position.

3.Turn off all electrical power to the unit.

4.DO NOT try to light the burners by hand. This appliance is equipped with an ignition device which automatically lights the burners.

5.Remove the access panel.

6.Turn the gas valve switch to the OFF position.

7.Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow B in the information on the unit safety label. If you don't smell gas, go to the next step.

8.Turn the gas valve switch to the ON position.

9.Replace the control access panel.

10.Turn on all electric power to the unit.

11.Set the thermostat to the desired setting.

12.If the unit will not operate, follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier.

To Turn Off Gas To Unit

1.Set the thermostat to the OFF position.

2.Turn off all electric power to the appliance if service is to be performed.

3.Remove the control access panel.

4.Turn the gas valve switch to the OFF position. DO NOT FORCE.

5.Replace the control access panel.

Post Start Check List

After the entire control circuit has been energized and the heating section is operating, make the following checks:

1.Check for gas leaks in the unit piping as well as the supply piping.

2.Check for correct manifold gas pressures. See Checking Gas Input.

3.Check the supply gas pressure. It must be within the limits shown on rating nameplate. Supply pressure should be checked with all gas appliances in the building at full fire. At no time should the standby gas line pressure exceed 13.5", nor the operating pressure drop below 4.5" for natural gas units. If gas pressure is outside these limits, contact the local gas utility for corrective action.

Manifold Gas Pressure Adjustment

Small adjustments to the gas flow may be made by turning the pressure regulator adjusting screw on the automatic gas valve. Refer to Figures 15 and 16.

Manual

 

Gas Switch

 

Pilot

 

Adjustment

 

(Remove Cap)

Electrical

 

 

Connection

Manifold

 

Pressure

 

Adjustment

½ NPT

(Remove Cap)

(Outlet)

Pilot Gas

Manifold

Connection

Pressure Tap

 

Figure 15: Single Stage Gas Valve Front

Unitary Products Group

25

Page 25
Image 25
York R-410A dimensions Start-Up, Circulating Fan, Prestart Check List, Operating Instructions, To Turn Off Gas To Unit