York R-410A Typical Field Power Wiring Diagram, Electrical Data, Minimum Circuit Ampacity

Models: R-410A

1 36
Download 36 pages 24.83 Kb
Page 12
Image 12
Figure 11: Typical Field Power Wiring Diagram

279550-YIM-A-0207

**= Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire.

2STAGE THERMOSTAT

R

G

UNIT CONTROL BOARD

TERMINAL STRIP

**R

G

NOTE: HEAT ANTICIPATOR SHOULD BE SET AT 0.35 AMPS FOR ALL MODELS.

Y1Y1

Y2Y/Y2

W1W1

W2W2

CC

24 VOLT

TRANSFORMER

PROGRAMMABLE

THERMOSTAT ONLY

Figure 10: Typical Field Control Wiring Diagram Two Stage Thermostat - Two Stage Gas Heat

Figure 11: Typical Field Power Wiring Diagram

Table 6: Electrical Data

 

 

Compressors

OD Fan

Supply

 

Max

 

 

 

 

Motors

Blower

MCA1

Fuse

2

/

 

Size

Volt

 

(each)

 

 

3

(Tons)

 

 

 

 

(each)

Motor

(Amps)

Breaker

 

 

RLA

LRA

 

MCC

FLA

FLA

Size

 

 

 

 

 

 

 

 

 

 

 

 

(Amps)

 

 

 

 

 

 

 

 

 

024

208/230-1-60

10.2

52

 

16

1.4

4.3

18.1

25

 

 

 

(2.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

208/230-1-60

16.6

82

 

26

0.9

9.1

30.7

40

 

 

 

208/230-3-60

11.1

58

 

17

0.9

9.1

23.8

30

 

 

 

(3.0)

 

 

 

 

460-3-60

4.5

29

 

7

0.5

4.6

10.7

15

 

 

 

 

 

 

 

 

048

208/230-1-60

21.1

96

 

33

1.8

9.1

36.3

45

 

 

 

208/230-3-60

13.4

88

 

21

1.8

9.1

26.7

35

 

 

 

(4.0)

 

 

 

 

460-3-60

6.4

41

 

10

0.9

4.6

13.0

15

 

 

 

 

 

 

 

 

1.Minimum Circuit Ampacity.

2.Maximum Over Current Protection per standard UL 1995.

3.Fuse or HACR circuit breaker size installed at factory or field installed.

12

Unitary Products Group

Page 12
Image 12
York R-410A Typical Field Power Wiring Diagram, Electrical Data, Minimum Circuit Ampacity, Unitary Products Group