**= Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire.
2STAGE THERMOSTAT
R
G
UNIT CONTROL BOARD
TERMINAL STRIP
**R
G
NOTE: HEAT ANTICIPATOR SHOULD BE SET AT 0.35 AMPS FOR ALL MODELS.
Y1Y1
Y2Y/Y2
W1W1
W2W2
CC
24 VOLT |
TRANSFORMER |
PROGRAMMABLE
THERMOSTAT ONLY
Figure 10: Typical Field Control Wiring Diagram Two Stage Thermostat - Two Stage Gas Heat
Figure 11: Typical Field Power Wiring Diagram
Table 6: Electrical Data
|
| Compressors | OD Fan | Supply |
| Max |
|
| ||||
|
| Motors | Blower | MCA1 | Fuse | 2 | / |
| ||||
Size | Volt |
| (each) |
|
| 3 | ||||||
(Tons) |
|
|
|
| (each) | Motor | (Amps) | Breaker |
| |||
| RLA | LRA |
| MCC | FLA | FLA | Size |
|
| |||
|
|
|
|
|
| |||||||
|
|
|
| (Amps) | ||||||||
|
|
|
|
|
|
|
|
| ||||
024 | 10.2 | 52 |
| 16 | 1.4 | 4.3 | 18.1 | 25 |
|
|
| |
(2.0) |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
036 | 16.6 | 82 |
| 26 | 0.9 | 9.1 | 30.7 | 40 |
|
|
| |
11.1 | 58 |
| 17 | 0.9 | 9.1 | 23.8 | 30 |
|
|
| ||
(3.0) |
|
|
|
| ||||||||
4.5 | 29 |
| 7 | 0.5 | 4.6 | 10.7 | 15 |
|
|
| ||
|
|
|
|
| ||||||||
048 | 21.1 | 96 |
| 33 | 1.8 | 9.1 | 36.3 | 45 |
|
|
| |
13.4 | 88 |
| 21 | 1.8 | 9.1 | 26.7 | 35 |
|
|
| ||
(4.0) |
|
|
|
| ||||||||
6.4 | 41 |
| 10 | 0.9 | 4.6 | 13.0 | 15 |
|
|
| ||
|
|
|
|
|
1.Minimum Circuit Ampacity.
2.Maximum Over Current Protection per standard UL 1995.
3.Fuse or HACR circuit breaker size installed at factory or field installed.