TABLE 2: REFRIGERANT CHARGE

UNIT (TONS)

MODEL

TYPE

FACTORY/ FIELD

 

CHARGE

 

CHARGED

SYS #1

SYS #2

SYS #3

SYS #4

 

 

 

25

wo/HGBP

R22

Factory

25 lb. / 8 oz.

26lb / 0oz

-

-

25

w/HGBP

R22

Factory

26 lb. / 0 oz.

26 lb. / 0oz

-

-

30

wo/HGBP

R22

Factory

13 lb. / 4 oz.

13 lb. / 8 oz.

13 lb. / 8 oz.

-

30

wo/HGBP1

R22

Factory

14 lb. / 6 oz.

14 lb. / 10 oz.

14 lb. / 10 oz.

-

30

w/HGBP

R22

Factory

14 lb. / 0 oz.

13 lb. / 8 oz.

13 lb. / 8 oz.

-

30

w/HGBP1

R22

Factory

15 lb. / 2 oz.

14 lb. / 10 oz.

14 lb. / 10 oz.

-

40

wo/HGBP

R22

Factory

15 lb. / 5 oz.

15 lb. / 4 oz.

15 lb. / 5 oz.

15 lb. / 15 oz.

40

w/HGBP

R22

Factory

15 lb. / 13 oz.

15 lb. / 4 oz.

15 lb. / 5 oz.

15 lb. / 15 oz.

1.With high capacity evaporator coil.

SELECTION PROCEDURE

GIVEN:

 

Required Cooling Capacity

460,000 Btuh

Required Sensible Cooling

390,000 Btuh

Required Heating (Gas)

320,000 Btuh

Entering Air on Evaporator

83° F DB/ 67° F WB

Outside Design Temperature

95° F

Supply Fan CFM

13,000 CFM

External Static Pressure

1.25 IWG

Electrical Supply Voltage

460-3-60

Economizer Required

 

2” Throw Away Filters

 

Constant Volume

 

SELECT UNIT:

1.Determine nominal tons:

460,000 / 12,000 = 38.33 Tons

Thus, a nominal 40 ton unit is selected.

2.Reference Cooling Capacity Table for a 40 ton unit with standard evaporator coil.

a.Locate the table for a standard evaporator coil with 95° F air on the condenser.

b.Enter table at 13,000 CFM and 67°F WB air on evaporator

c.Trace to 83° F Entering Dry Bulb column.

d.Read 493 MBH total capacity and 403 MBH sensi- ble capacity.

The 40 ton unit will meet the cooling requirements. From the nomenclature, the unit will be a Y34. Choose the appropriate configuration for the next digit. Assuming bottom return and supply, the fourth digit would be an “A,” making the model Y34A.

3.Find Gas Heating Capacity Table.

a.Trace down Output column.

b.Find output which exceeds 320,000 Btuh require- ment. The N5 option gives 426 MBH output.

c.Ensure that it is offered in the Y34 unit. Read option model as N5.

From the basic nomenclature, the model now becomes Y34AN5. Add voltage code of “4” for 460-3-60. Nomen- clature becomes Y34AN54.

SELECT FAN SPEED AND HORSEPOWER REQUIREMENTS OF SUPPLY AIR FAN

1.Find Supply Air Performance Tables for the 40 ton unit.

a.Check footnotes and make necessary additions or deductions to static resistance of ductwork:

Ductwork static resistance

1.25

IWG

Economizer static resistance addition

 

 

(interpolate) =.25 IWG + Gas Heat (High) =

0.5

IWG

Total Static Resistance

2.0

IWG

b.Enter Fan Performance Table at 13,000 CFM and

2.0 IWG static pressure:

RPM = 690

BHP = 10.7

NOTE: Either a Class I or Class II blower could be used.

c.Enter the Fan Motor Drive Tables. Selecting a 15 hp motor allows (service factor of 1.5) for a maximum operating BHP greater than the 10.7 BHP require- ment.

SIZE OVERCURRENT PROTECTION DEVICE AND DETERMINE CIRCUIT AMPACITY

1.Find electrical tables for the basic 40 ton unit.

a.Enter table for 460-3-60 voltage.

b.Find 15 hp in the Supply Air Fan column.

c.Trace to Minimum Circuit Ampacity column - read 104.

d.Trace to Max. Fuse/Breaker Size column - read 110.

e.Size wire and overprotection device accordingly.

f.Check all footnotes.

Johnson Controls Unitary Products

11

Page 11
Image 11
York Y32, Y33, Y34 manual Selection Procedure, Refrigerant Charge, Select Unit, Unit Tons Model Type

Y32, Y34, Y33 specifications

The York Y33, Y32, and Y34 series represents a significant advancement in rooftop packaged units designed for commercial HVAC applications. These models are known for their reliability, energy efficiency, and innovative features that cater to diverse climate control needs.

The York Y33 series introduces modern features aimed at maximizing comfort and reducing energy costs. Its sleek design and compact size make it a versatile option for various applications, including retail spaces, office buildings, and industrial facilities. One of the standout features of the Y33 is its variable-speed compressor technology. This allows the unit to adjust its cooling output based on real-time demand, resulting in notable energy savings compared to traditional single-speed units.

The Y32 model builds upon the strengths of the Y33, offering enhanced capabilities for large commercial spaces. It incorporates advanced controls and building management system (BMS) connectivity, enabling seamless integration into existing infrastructure. The Y32 is designed with a focus on ease of maintenance and serviceability, featuring accessible components that streamline repair processes.

The York Y34 series emphasizes environmentally friendly practices, utilizing low-GWP refrigerants that minimizes its impact on the environment. It also boasts improved heat exchangers that increase efficiency and performance. The Y34’s design minimizes noise levels, making it ideal for applications where quiet operation is paramount, such as schools and healthcare facilities.

All three models share several key technologies, including fan and motor designs that optimize airflow while reducing energy consumption. Additionally, the series features enhanced insulation, significantly improving thermal performance and reducing the risk of condensation-related issues.

In summary, the York Y33, Y32, and Y34 models represent a commitment to innovation in commercial HVAC systems. Their combination of advanced technology, energy efficiency, and user-friendly design makes them suitable for a variety of applications while promoting sustainability and operational cost-effectiveness. Investing in these units not only supports optimal indoor climate control but also aligns with the growing demand for eco-friendly solutions in today’s commercial landscape.