TABLE 2: REFRIGERANT CHARGE
UNIT (TONS) | MODEL | TYPE | FACTORY/ FIELD |
| CHARGE |
| ||
CHARGED | SYS #1 | SYS #2 | SYS #3 | SYS #4 | ||||
|
|
| ||||||
25 | wo/HGBP | R22 | Factory | 25 lb. / 8 oz. | 26lb / 0oz | - | - | |
25 | w/HGBP | R22 | Factory | 26 lb. / 0 oz. | 26 lb. / 0oz | - | - | |
30 | wo/HGBP | R22 | Factory | 13 lb. / 4 oz. | 13 lb. / 8 oz. | 13 lb. / 8 oz. | - | |
30 | wo/HGBP1 | R22 | Factory | 14 lb. / 6 oz. | 14 lb. / 10 oz. | 14 lb. / 10 oz. | - | |
30 | w/HGBP | R22 | Factory | 14 lb. / 0 oz. | 13 lb. / 8 oz. | 13 lb. / 8 oz. | - | |
30 | w/HGBP1 | R22 | Factory | 15 lb. / 2 oz. | 14 lb. / 10 oz. | 14 lb. / 10 oz. | - | |
40 | wo/HGBP | R22 | Factory | 15 lb. / 5 oz. | 15 lb. / 4 oz. | 15 lb. / 5 oz. | 15 lb. / 15 oz. | |
40 | w/HGBP | R22 | Factory | 15 lb. / 13 oz. | 15 lb. / 4 oz. | 15 lb. / 5 oz. | 15 lb. / 15 oz. |
1.With high capacity evaporator coil.
SELECTION PROCEDURE
GIVEN: |
|
Required Cooling Capacity | 460,000 Btuh |
Required Sensible Cooling | 390,000 Btuh |
Required Heating (Gas) | 320,000 Btuh |
Entering Air on Evaporator | 83° F DB/ 67° F WB |
Outside Design Temperature | 95° F |
Supply Fan CFM | 13,000 CFM |
External Static Pressure | 1.25 IWG |
Electrical Supply Voltage | |
Economizer Required |
|
2” Throw Away Filters |
|
Constant Volume |
|
SELECT UNIT:
1.Determine nominal tons:
460,000 / 12,000 = 38.33 Tons
Thus, a nominal 40 ton unit is selected.
2.Reference Cooling Capacity Table for a 40 ton unit with standard evaporator coil.
a.Locate the table for a standard evaporator coil with 95° F air on the condenser.
b.Enter table at 13,000 CFM and 67°F WB air on evaporator
c.Trace to 83° F Entering Dry Bulb column.
d.Read 493 MBH total capacity and 403 MBH sensi- ble capacity.
The 40 ton unit will meet the cooling requirements. From the nomenclature, the unit will be a Y34. Choose the appropriate configuration for the next digit. Assuming bottom return and supply, the fourth digit would be an “A,” making the model Y34A.
3.Find Gas Heating Capacity Table.
a.Trace down Output column.
b.Find output which exceeds 320,000 Btuh require- ment. The N5 option gives 426 MBH output.
c.Ensure that it is offered in the Y34 unit. Read option model as N5.
From the basic nomenclature, the model now becomes Y34AN5. Add voltage code of “4” for
SELECT FAN SPEED AND HORSEPOWER REQUIREMENTS OF SUPPLY AIR FAN
1.Find Supply Air Performance Tables for the 40 ton unit.
a.Check footnotes and make necessary additions or deductions to static resistance of ductwork:
Ductwork static resistance | 1.25 | IWG |
Economizer static resistance addition |
|
|
(interpolate) =.25 IWG + Gas Heat (High) = | 0.5 | IWG |
Total Static Resistance | 2.0 | IWG |
b.Enter Fan Performance Table at 13,000 CFM and
2.0 IWG static pressure:
RPM = 690
BHP = 10.7
NOTE: Either a Class I or Class II blower could be used.
c.Enter the Fan Motor Drive Tables. Selecting a 15 hp motor allows (service factor of 1.5) for a maximum operating BHP greater than the 10.7 BHP require- ment.
SIZE OVERCURRENT PROTECTION DEVICE AND DETERMINE CIRCUIT AMPACITY
1.Find electrical tables for the basic 40 ton unit.
a.Enter table for
b.Find 15 hp in the Supply Air Fan column.
c.Trace to Minimum Circuit Ampacity column - read 104.
d.Trace to Max. Fuse/Breaker Size column - read 110.
e.Size wire and overprotection device accordingly.
f.Check all footnotes.