York Y33, Y34, Y32 manual Standard Gas Heating Capacities, Temperature Rise, Minimum Heating Cfm

Models: Y32 Y34 Y33

1 96
Download 96 pages 54.91 Kb
Page 12
Image 12
TABLE 3: STANDARD GAS HEATING CAPACITIES

246653-YTG-E-0108

TABLE 3: STANDARD GAS HEATING CAPACITIES

GAS HEAT

AVAILABLE ON

INPUT CAPACITY (MBH)1

OUTPUT

GAS RATE, CU. FT./HR.3

 

 

CAPACITY

 

 

OPTION

MODELS

1ST STAGE

TOTAL

1ST STAGE

TOTAL

(MBH)2

N3

Y32/Y33/Y34

267

267

213

247

247

N5

Y32/Y33/Y34

267

533

426

247

495

N8

Y34 ONLY

2674

800

638

247

742

1.Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.

2.Blower motor heat not included.

3.Based on a heat content of 1075 Btu/Ft.3

4.Unit Control Board with 3 heating outputs only. For all other Unit Control Boards the 1st Stage is 533 MBH.

TABLE 4: TEMPERATURE RISE

TON

 

MODULES

 

 

 

 

 

1

2

3

25

5-35

25-55

-

30

5-35

20-50

-

40

5-30

10-45

25-55

TABLE 5: MINIMUM HEATING CFM

TON

 

MODULES

 

 

 

 

 

1

2

3

25

5,644

7,183

-

30

5,644

7,901

-

40

6,584

8,779

13,169

TABLE 6: MODULATING GAS HEATING CAPACITIES

GAS HEAT OPTION

AVAILABLE ON

INPUT CAPACITY (MBH)

STEPS

OUTPUT CAPACITY

GAS RATE, CU. FT./HR.

MODELS

MINIMUM

MAXIMUM

(MBH)1

MINIMUM

MAXIMUM

D32

 

Y32/Y33/Y34

69

267

6

213

64

247

D52

Y32/Y33/Y34

69

533

12

426

64

495

D82

Y34 ONLY

69

800

17

638

64

744

1.Output Capacity at Full Fire.

2.Modulating Gas Heat available on CV models only.

12

Johnson Controls Unitary Products

Page 12
Image 12
York Y33, Y34 Standard Gas Heating Capacities, Temperature Rise, Minimum Heating Cfm, Modulating Gas Heating Capacities