246653-YTG-E-0108

TABLE 38: FAN PERFORMANCE - 30 TON 1, 2

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (IWG)

 

 

 

 

 

AIRFLOW (CFM)

 

0.2

0.4

 

 

0.6

 

0.8

 

1.0

 

RPM

 

BHP3

RPM

 

BHP3

RPM

 

BHP3

RPM

 

BHP3

RPM

 

BHP3

6000

321

 

0.9

373

 

1.2

422

 

1.6

469

 

1.9

513

 

2.2

7000

357

 

1.4

404

 

1.7

447

 

2.0

490

 

2.3

529

 

2.7

8000

398

 

1.9

437

 

2.2

477

 

2.6

515

 

3.0

551

 

3.5

9000

436

 

2.6

473

 

2.9

509

 

3.4

543

 

3.8

577

 

4.2

10000

477

 

3.4

511

 

3.9

543

 

4.3

575

 

4.7

606

 

5.3

11000

519

 

4.4

549

 

4.9

579

 

5.4

609

 

5.9

637

 

6.4

12000

560

 

5.7

589

 

6.2

617

 

6.7

643

 

7.2

670

 

7.8

13000

603

 

7.1

629

 

7.7

654

 

8.2

680

 

8.8

705

 

9.3

14000

645

 

8.8

669

 

9.3

694

 

10.0

718

 

10.5

741

 

11.2

15000

688

 

10.7

711

 

11.3

733

 

12.1

755.6

 

12.7

778

 

13.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (IWG)

 

 

 

 

 

AIRFLOW (CFM)

 

1.2

1.4

 

 

1.6

 

1.8

 

2.0

 

RPM

 

BHP3

RPM

 

BHP3

RPM

 

BHP3

RPM

 

BHP3

RPM

 

BHP3

6000

554

 

2.5

596

 

2.9

632

 

3.4

668

 

3.7

703

 

4.1

7000

568

 

3.2

607

 

3.6

642

 

4.0

676

 

4.4

710

 

4.8

8000

587

 

3.9

622

 

4.3

655

 

4.7

689

 

5.3

720

 

5.7

9000

610

 

4.7

642

 

5.1

673

 

5.7

704

 

6.2

734

 

6.7

10000

636

 

5.8

666

 

6.3

695

 

6.8

723

 

7.4

751

 

7.9

11000

665

 

6.9

693

 

7.5

720

 

8.0

746

 

8.6

773

 

9.2

12000

697

 

8.3

722

 

8.9

747

 

9.6

772

 

10.1

797

 

10.7

13000

729

 

10.0

753

 

10.5

777

 

11.2

801

 

11.9

824

 

12.5

14000

764

 

11.9

787

 

12.5

809

 

13.2

831

 

13.9

853

 

14.5

15000

800

 

14.0

821

 

14.6

842

 

15.3

863

 

16.0

884

 

16.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (IWG)

 

 

 

 

 

AIRFLOW (CFM)

 

2.2

2.4

 

 

2.6

 

2.8

 

3.0

 

RPM

 

BHP3

RPM

 

BHP3

RPM

 

BHP3

RPM

 

BHP3

RPM

 

BHP3

6000

734

 

4.5

765

 

4.9

796

 

5.4

824

 

5.8

850

 

6.3

7000

741

 

5.3

772

 

5.8

803

 

6.3

830

 

6.7

858

 

7.2

8000

750

 

6.2

781

 

6.7

810

 

7.2

837

 

7.8

865

 

8.3

9000

763

 

7.2

792

 

7.8

820

 

8.3

847

 

8.9

873

 

9.5

10000

779

 

8.4

807

 

9.0

833

 

9.6

859

 

10.2

885

 

10.8

11000

799

 

9.8

824

 

10.4

849

 

11.0

874

 

11.7

899

 

12.3

12000

821

 

11.3

845

 

12.1

869

 

12.7

893

 

13.3

916

 

14.1

13000

847

 

13.2

869

 

13.9

892

 

14.6

914

 

15.2

936

 

15.9

14000

874

 

15.2

896

 

15.9

917

 

16.6

938

 

17.3

959

 

18.1

15000

904

 

17.4

924

 

18.3

944

 

19.0

964

 

19.7

984

 

20.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (IWG)

 

 

 

 

 

AIRFLOW (CFM)

 

3.2

3.4

 

 

3.6

 

3.8

 

4.0

 

RPM

 

BHP3

RPM

 

BHP3

RPM

 

BHP3

RPM

 

BHP3

RPM

 

BHP3

6000

877

 

6.7

904

 

7.1

928

 

7.7

951

 

8.1

975

 

8.6

7000

885

 

7.7

911

 

8.2

935

 

8.7

959

 

9.2

984

 

9.7

8000

892

 

8.8

917

 

9.3

942

 

9.9

966

 

10.4

991

 

10.9

9000

900

 

10.0

925

 

10.6

949

 

11.1

974

 

11.8

998

 

12.4

10000

910

 

11.4

934

 

12.1

958

 

12.7

982

 

13.3

1006

 

14.0

11000

923

 

13.0

946

 

13.7

970

 

14.3

993

 

14.9

1015

 

15.5

12000

939

 

14.7

961

 

15.3

984

 

16.1

1006

 

16.8

1028

 

17.5

13000

958

 

16.6

980

 

17.3

1001

 

18.1

1022

 

18.8

1043

 

19.5

14000

980

 

18.8

1001

 

19.6

1021

 

20.4

1040

 

21.1

1060

 

21.8

15000

1004

 

21.2

1023

 

22.1

1043

 

22.9

1062

 

23.6

1081

 

24.5

1.Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.

2.Refer to Tables 10, 15, 21 and 42 for component additions and deductions to fan performance tables.

3.BHP includes drive losses.

4.Shaded RPMs require Class II blower.

48

Johnson Controls Unitary Products

Page 48
Image 48
York Y33, Y34, Y32 manual FAN Performance 30 TON 1, RPM BHP3

Y32, Y34, Y33 specifications

The York Y33, Y32, and Y34 series represents a significant advancement in rooftop packaged units designed for commercial HVAC applications. These models are known for their reliability, energy efficiency, and innovative features that cater to diverse climate control needs.

The York Y33 series introduces modern features aimed at maximizing comfort and reducing energy costs. Its sleek design and compact size make it a versatile option for various applications, including retail spaces, office buildings, and industrial facilities. One of the standout features of the Y33 is its variable-speed compressor technology. This allows the unit to adjust its cooling output based on real-time demand, resulting in notable energy savings compared to traditional single-speed units.

The Y32 model builds upon the strengths of the Y33, offering enhanced capabilities for large commercial spaces. It incorporates advanced controls and building management system (BMS) connectivity, enabling seamless integration into existing infrastructure. The Y32 is designed with a focus on ease of maintenance and serviceability, featuring accessible components that streamline repair processes.

The York Y34 series emphasizes environmentally friendly practices, utilizing low-GWP refrigerants that minimizes its impact on the environment. It also boasts improved heat exchangers that increase efficiency and performance. The Y34’s design minimizes noise levels, making it ideal for applications where quiet operation is paramount, such as schools and healthcare facilities.

All three models share several key technologies, including fan and motor designs that optimize airflow while reducing energy consumption. Additionally, the series features enhanced insulation, significantly improving thermal performance and reducing the risk of condensation-related issues.

In summary, the York Y33, Y32, and Y34 models represent a commitment to innovation in commercial HVAC systems. Their combination of advanced technology, energy efficiency, and user-friendly design makes them suitable for a variety of applications while promoting sustainability and operational cost-effectiveness. Investing in these units not only supports optimal indoor climate control but also aligns with the growing demand for eco-friendly solutions in today’s commercial landscape.