York Y32, Y33, Y34 manual COMPONENT STATIC RESISTANCE1

Models: Y32 Y34 Y33

1 96
Download 96 pages 54.91 Kb
Page 56
Image 56
TABLE 42: COMPONENT STATIC RESISTANCE1, 2

246653-YTG-E-0108

TABLE 42: COMPONENT STATIC RESISTANCE1, 2

COMPONENT COIL

 

 

 

CFM

 

 

 

LOSSES

6,000

8,000

10,000

12,000

14,000

16,000

18,000

STD. 25 TON, DRY

-0.06

-0.08

-0.10

-0.13

-

-

-

STD. 25 TON, WET

Baseline

Baseline

Baseline

Baseline

Baseline

Baseline

Baseline

 

 

 

 

 

 

 

 

STD. 30 TON, DRY

-0.045

-0.075

-0.112

-0.157

-0.207

-0.264

-0.326

 

 

 

 

 

 

 

 

STD. 30 TON, WET

Baseline

Baseline

Baseline

Baseline

Baseline

Baseline

Baseline

 

 

 

 

 

 

 

 

HI CAP 30 TON, DRY

-0.019

-0.035

-0.052

-0.073

-0.098

-0.124

-0.155

 

 

 

 

 

 

 

 

HI CAP 30 TON, WET

0.042

0.069

0.103

0.142

0.186

0.236

0.290

 

 

 

 

 

 

 

 

STD. 40 TON, DRY

-0.030

-0.051

-0.076

-0.106

-0.140

-0.177

-0.219

 

 

 

 

 

 

 

 

STD. 40 TON, WET

Baseline

Baseline

Baseline

Baseline

Baseline

Baseline

Baseline

 

 

 

 

 

 

 

 

HI CAP 40 TON, DRY

-0.020

-0.033

-0.050

-0.069

-0.092

-0.116

-0.144

 

 

 

 

 

 

 

 

HI CAP 40 TON, WET

0.023

0.038

0.057

0.079

0.105

0.133

0.164

 

 

 

 

 

 

 

 

FILTER LOSSES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2” TA OR HI EFF.

Baseline

Baseline

Baseline

Baseline

Baseline

Baseline

Baseline

 

 

 

 

 

 

 

 

RIGID 6”, 65%

0.048

0.080

0.119

0.165

0.217

0.274

0.338

 

 

 

 

 

 

 

 

RIGID 6”, 95%

0.189

0.308

0.448

0.609

0.790

0.988

1.205

 

 

 

 

 

 

 

 

IGV LOSSES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25 & 30 TON

0.048

0.085

0.132

0.190

0.259

0.338

0.428

 

 

 

 

 

 

 

 

40 TON

0.027

0.049

0.076

0.110

0.149

0.195

0.246

 

 

 

 

 

 

 

 

GAS HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

267 MBH HEAT

0.106

0.141

0.177

0.212

0.247

0.283

0.318

 

 

 

 

 

 

 

 

533 MBH HEAT

0.212

0.283

0.353

0.424

0.495

0.566

0.636

 

 

 

 

 

 

 

 

800 MBH HEAT

0.318

0.423

0.531

0.636

0.741

0.849

0.954

 

 

 

 

 

 

 

 

ELECTRIC HEAT

0.050

0.100

0.150

0.310

0.430

0.530

0.680

 

 

 

 

 

 

 

 

ECONOMIZER

0.063

0.104

0.153

0.210

0.276

0.349

0.429

 

 

 

 

 

 

 

 

POWER EXHAUST

0.046

0.081

0.127

0.182

0.248

0.324

0.410

1.Baseline losses based on system/cabinet effects, wet standard coil and 2” throwaway filters at 70°F, 0 feet elevation with standard air.

2.See Tables 10, 12, 15, 18, 21 and 23 for hot water and steam water coil static resistance.

56

Johnson Controls Unitary Products

Page 56
Image 56
York Y32, Y33, Y34 manual COMPONENT STATIC RESISTANCE1