TABLE 37: FAN PERFORMANCE - 25 TON1, 2
|
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (IWG) |
|
|
|
| |||||
AIRFLOW CFM |
| 0.2 | 0.4 |
| 0.6 |
| 0.8 |
|
| 1.0 | |||||
| RPM |
| BHP3 | RPM |
| BHP3 | RPM |
| BHP3 | RPM |
| BHP3 | RPM |
| BHP3 |
4000 | - |
| - | 342 |
| 0.6 | 404 |
| 0.9 | 456 |
| 1.1 | 506 |
| 1.4 |
5000 | 306 |
| 0.7 | 362 |
| 0.9 | 415 |
| 1.1 | 465 |
| 1.4 | 512 |
| 1.7 |
6000 | 337 |
| 1.0 | 387 |
| 1.2 | 433 |
| 1.5 | 478 |
| 1.8 | 521 |
| 2.1 |
7000 | 370 |
| 1.4 | 415 |
| 1.7 | 456 |
| 2.0 | 497 |
| 2.3 | 535 |
| 2.7 |
8000 | 408 |
| 2.0 | 446 |
| 2.3 | 484 |
| 2.6 | 520 |
| 2.9 | 555 |
| 3.3 |
9000 | 444 |
| 2.7 | 480 |
| 3.0 | 514 |
| 3.4 | 547 |
| 3.8 | 579 |
| 4.2 |
10000 | 481 |
| 3.6 | 514 |
| 3.9 | 545 |
| 4.3 | 576 |
| 4.7 | 606 |
| 5.1 |
11000 | 520 |
| 4.6 | 550 |
| 5.0 | 579 |
| 5.4 | 608 |
| 5.8 | 635 |
| 6.3 |
12000 | 557 |
| 5.8 | 585 |
| 6.3 | 612 |
| 6.7 | 638 |
| 7.1 | 664 |
| 7.5 |
13000 | 596 |
| 7.2 | 622 |
| 7.7 | 647 |
| 8.1 | 671 |
| 8.6 | 696 |
| 9.1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (IWG) |
|
|
|
| |||||
AIRFLOW CFM |
| 1.2 | 1.4 |
| 1.6 |
| 1.8 |
|
| 2.0 | |||||
| RPM |
| BHP3 | RPM |
| BHP3 | RPM |
| BHP3 | RPM |
| BHP3 | RPM |
| BHP3 |
4000 | 549 |
| 1.7 | 591 |
| 2.0 | 628 |
| 2.3 | 663 |
| 2.7 | 698 |
| 3.0 |
5000 | 555 |
| 2.1 | 597 |
| 2.4 | 634 |
| 2.8 | 670 |
| 3.2 | 705 |
| 3.5 |
6000 | 562 |
| 2.5 | 602 |
| 2.9 | 638 |
| 3.3 | 674 |
| 3.7 | 709 |
| 4.1 |
7000 | 573 |
| 3.0 | 610 |
| 3.4 | 645 |
| 3.9 | 679 |
| 4.3 | 713 |
| 4.7 |
8000 | 591 |
| 3.7 | 624 |
| 4.1 | 657 |
| 4.6 | 689 |
| 5.0 | 720 |
| 5.4 |
9000 | 611 |
| 4.6 | 642 |
| 5.0 | 673 |
| 5.4 | 703 |
| 5.9 | 732 |
| 6.4 |
10000 | 634 |
| 5.5 | 663 |
| 6.0 | 692 |
| 6.4 | 719 |
| 6.9 | 747 |
| 7.4 |
11000 | 662 |
| 6.7 | 689 |
| 7.2 | 715 |
| 7.6 | 741 |
| 8.1 | 766 |
| 8.6 |
12000 | 690 |
| 8.0 | 714 |
| 8.5 | 739 |
| 9.0 | 763 |
| 9.5 | 787 |
| 10.0 |
13000 | 720 |
| 9.6 | 743 |
| 10.1 | 766 |
| 10.6 | 789 |
| 11.2 | 811 |
| 11.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (IWG) |
|
|
|
| |||||
AIRFLOW CFM |
| 2.2 | 2.4 |
| 2.6 |
| 2.8 |
|
| 3.0 | |||||
| RPM |
| BHP3 | RPM |
| BHP3 | RPM |
| BHP3 | RPM |
| BHP3 | RPM |
| BHP3 |
4000 | 728 |
| 3.3 | 757 |
| 3.7 | 787 |
| 4.1 | 814 |
| 4.4 | 839 |
| 4.8 |
5000 | 736 |
| 3.9 | 767 |
| 4.3 | 798 |
| 4.7 | 825 |
| 5.1 | 851 |
| 5.5 |
6000 | 740 |
| 4.5 | 772 |
| 5.0 | 803 |
| 5.4 | 830 |
| 5.9 | 858 |
| 6.3 |
7000 | 744 |
| 5.2 | 775 |
| 5.6 | 805 |
| 6.1 | 833 |
| 6.6 | 861 |
| 7.1 |
8000 | 751 |
| 6.0 | 781 |
| 6.5 | 810 |
| 7.0 | 837 |
| 7.5 | 865 |
| 8.0 |
9000 | 760 |
| 6.9 | 789 |
| 7.4 | 817 |
| 7.9 | 843 |
| 8.4 | 870 |
| 9.0 |
10000 | 774 |
| 7.9 | 801 |
| 8.4 | 826 |
| 9.0 | 852 |
| 9.5 | 878 |
| 10.1 |
11000 | 792 |
| 9.2 | 817 |
| 9.7 | 841 |
| 10.2 | 865 |
| 10.8 | 890 |
| 11.4 |
12000 | 811 |
| 10.6 | 834 |
| 11.2 | 857 |
| 11.8 | 880 |
| 12.4 | 903 |
| 13.0 |
13000 | 833 |
| 12.3 | 855 |
| 12.9 | 877 |
| 13.5 | 899 |
| 14.1 | 921 |
| 14.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (IWG) |
|
|
|
| |||||
AIRFLOW CFM |
| 3.2 | 3.4 |
| 3.6 |
| 3.8 |
|
| 4.0 | |||||
| RPM |
| BHP3 | RPM |
| BHP3 | RPM |
| BHP3 | RPM |
| BHP3 | RPM |
| BHP3 |
4000 | 864 |
| 5.1 | 890 |
| 5.5 | 913 |
| 5.9 | 935 |
| 6.3 | 957 |
| 6.7 |
5000 | 878 |
| 6.0 | 904 |
| 6.4 | 927 |
| 6.8 | 950 |
| 7.3 | 973 |
| 7.7 |
6000 | 885 |
| 6.8 | 911 |
| 7.3 | 935 |
| 7.7 | 959 |
| 8.2 | 983 |
| 8.7 |
7000 | 889 |
| 7.6 | 914 |
| 8.1 | 939 |
| 8.7 | 964 |
| 9.2 | 988 |
| 9.7 |
8000 | 892 |
| 8.5 | 918 |
| 9.1 | 942 |
| 9.6 | 967 |
| 10.2 | 992 |
| 10.8 |
9000 | 897 |
| 9.5 | 921 |
| 10.1 | 946 |
| 10.7 | 970 |
| 11.3 | 995 |
| 11.9 |
10000 | 903 |
| 10.7 | 927 |
| 11.3 | 951 |
| 11.9 | 975 |
| 12.6 | 999 |
| 13.2 |
11000 | 913 |
| 12.1 | 936 |
| 12.7 | 959 |
| 13.3 | 983 |
| 14.0 | 1005 |
| 14.6 |
12000 | 926 |
| 13.6 | 948 |
| 14.2 | 970 |
| 14.8 | 992 |
| 15.4 | 1013 |
| 16.1 |
13000 | 942 |
| 15.3 | 963 |
| 15.9 | 984 |
| 16.6 | 1005 |
| 17.3 | 1025 |
| 18.0 |
1.Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
2.Refer to Tables 10, 15, 21 and 42 for component additions and deductions to fan performance tables.
3.BHP includes drive losses.
4.Shaded RPMs require Class II blower.
46 | Johnson Controls Unitary Products |