Design Parameters

FORM 150.64-EG1

ENGLISH

YCAL

LEAVING WATER

COOLER FLOW (GPM)

AIR ON CONDENSER (°F)

TEMPERATURE (°F)

 

 

 

 

 

 

MIN

MAX

MIN

MAX

MIN

MAX

0041

40

55

40

200

0

125

0045

40

55

40

200

0

125

0051

40

55

40

200

0

125

0055

40

55

60

300

0

125

0061

40

55

60

300

0

125

0065

40

55

60

300

0

125

 

 

 

 

 

 

 

 

 

 

SI UNITS

 

 

 

YCAL

LEAVING WATER

COOLER FLOW (L/S)

AIR ON CONDENSER (°C)

TEMPERATURE (°DC)

 

 

 

 

 

 

MIN

MAX

MIN

MAX

MIN

MAX

0041

4.4

12.8

2.5

12.6

-17.7

51.7

0045

4.4

12.8

2.5

12.6

-17.7

51.7

0051

4.4

12.8

2.5

12.6

-17.7

51.7

0055

4.4

12.8

3.8

18.9

-17.7

51.7

0061

4.4

12.8

3.8

18.9

-17.7

51.7

0065

4.4

12.8

3.8

18.9

-17.7

51.7

NOTES:

1.For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK Office for application requirements.

2.For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK Office for application guidelines.

3.The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.

4.For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed on the system (for YCAL0041-0065 models only).

5.For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.