Dimensions - YCAL0051 (SI)

171

 

82

22 TYP.

 

100

VIEW B-B

BOTTOM OF PANEL

1213

LIQUID IN

ELECTRICAL ACCESS

PANEL

1192

879

 

252

 

401

LIQUID OUT

76 VICTAULIC (typ)

321

 

 

1146

2292 BASE WIDTH

LEFT END

Aluminum

YCAL

Center of Gravity (in.)

X

Y

 

0051

1504.6

1082.4

 

Copper

 

YCAL

Center of Gravity (in.)

X

Y

 

0051

1633.0

1090.8

NOTE: All dimensions are in mm unless specified otherwise.

NOTE:

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m; rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall - 2m; top – no obstructions allowed; distance between adjacent units – 3m. No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by 152mm.

50

YORK INTERNATIONAL

Page 50
Image 50
York YCAL0041, YCAL0065 manual Dimensions YCAL0051 SI, 0051 1504.6 1082.4 Copper, 0051 1633.0 1090.8