Dimensions -YCAL0055 (SI)

1590

171

 

82

22 TYP.

 

100VIEW B-B BOTTOM OF PANEL

LIQUID IN

1572

ELECTRICAL ACCESS

 

PANEL

880

 

252

 

401

LIQUID OUT

76 VICTAULIC (typ)

321

 

 

1146

2292 BASE WIDTH

LEFT END

Aluminum

YCAL

Center of Gravity (in.)

X

Y

 

0055

1470.3

1092.0

 

Copper

 

YCAL

Center of Gravity (in.)

X

Y

 

0055

1586.9

1098.3

NOTE: All dimensions are in mm unless specified otherwise.

NOTE:

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m; rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall - 2m; top – no obstructions allowed; distance between adjacent units – 3m. No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by 152mm.

52

YORK INTERNATIONAL

Page 52
Image 52
York YCAL0041, YCAL0065 manual Dimensions -YCAL0055 SI