Dimensions - YCAL0061 (English)

Dimensions - YCAL0061 (English)

62 5/8"

6 3/4"

 

3 1/4"

7/8" TYP.

 

3 15/16"

VIEW B-B

 

BOTTOM OF PANEL

LIQUID IN

61 7/8"

 

ELECTRICAL ACCESS

 

 

PANEL

 

 

34 11/16"

 

 

9 15/16"

 

 

15 3/4"

 

LIQUID OUT

3" VICTAULIC (typ)

 

12 5/8"

 

 

 

 

43 1/8"

90 1/4" BASE WIDTH

LEFT END

Aluminum

YCAL

Center of Gravity (in.)

X

Y

 

0061

56.6

45.2

 

Copper

 

YCAL

Center of Gravity (in.)

X

Y

 

0061

61.8

45.8

NOTE:

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli- able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall

6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by 6".