York YCAL0065, YCAL0041 manual Voltage Range

Models: YCAL0065 YCAL0041

1 80
Download 80 pages 43.99 Kb
Page 63
Image 63
VOLTAGE RANGE

FORM 150.64-EG1

UNIT VOLTAGE

 

 

CONTROL

MCA

OVER CURRENT PROTECTION,

 

 

 

POWER

 

SEE NOTE B

NF DISC Sw

 

UNIT

 

NOTE A

 

MODELS w/o

 

 

MIN

 

MAX

 

VOLTAGE

 

 

 

 

 

CONTROL

 

115-1-60/50

15A

10A

 

15A

30 A / 240V

 

 

 

TRANS

 

 

 

 

 

 

 

 

 

 

 

 

 

-17

 

200-1-60

15A

10A

 

15A

30 A / 240V

MODELS w/

-28

 

230-1-60

15A

10A

 

15A

30 A / 240V

-40

 

380-1-60

15A

10A

 

15A

30 A / 480V

CONTROL

 

 

-46

 

460-1-60

15A

10A

 

15A

30 A / 480V

TRANS

 

 

-50

 

380/415-1-60

15A

10A

 

15A

30A / 415V

 

 

 

 

-58

 

575-1-60

15A

10A

 

15A

30 A / 600V

A. Minimum #14 AWG, 75°C, Copper Recommended

 

 

 

 

 

 

B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker

VOLTAGE RANGE

VOLTAGE CODE

 

UNIT POWER

 

MIN.

 

MAX.

-17

 

200-3-60

 

180

 

220

-28

 

230-3-60

 

207

 

253

-40

 

380/415-3-60

 

342

 

440

-46

 

460-3-60

 

414

 

506

-50

 

380/415-3-50

 

342

 

440

-58

 

575-3-60

 

517

 

633

LEGEND

ACROSS THE LINE START

 

ACR-LINE

 

C.B.

CIRCUIT BREAKER

 

 

 

D.E.

DUAL ELEMENT FUSE

 

 

 

DISC SW

DISCONNECT SWITCH

 

 

 

FACT MOUNT CB

FACTORY MOUNTED CIRCUIT BREAKER

 

FLA

FULL LOAD AMPS

 

 

 

HZ

HERTZ

 

 

 

MAX

MAXIMUM

 

 

 

MCA

MINIMUM CIRCUIT AMPACITY

 

MIN

MINIMUM

 

 

 

MIN NF

MINIMUM NON FUSED

 

 

 

RLA

RATED LOAD AMPS

 

 

 

S.P. WIRE

SINGLE POINT WIRING

 

 

 

UNIT MTD SERV SW

UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT

LRA

SWITCH)

 

 

 

LOCKED ROTOR AMPS

 

 

 

YORK INTERNATIONAL

63

Page 63
Image 63
York YCAL0065, YCAL0041 manual Voltage Range