GENERAL

The Liquid Chiller will be completely assembled with all interconnecting refrigerant piping and internal wiring, ready for field installation.

The unit will be pressure-tested, evacuated, and charged with Refrigerant-22, and York ‘L’ (POE) synthetic oil. There will be an operational test, with water flowing through the cooler, to check that each control device operates correctly.

The unit will be covered with a coat of Caribbean Blue enamel. Units are designed in accordance with NFPA 70 (National Electric Code), U.L. and cU.L. Standards, ASHRAE/ANSI 15 Safety Code for Mechanical Refrig- eration. All units are produced at an ISO 9001 regis- tered facility. All YCWS chillers are rated and certified in accordance with ARI Standard 550/590 at ARI condi- tions.

SEMI-HERMETIC YORK SCREW COMPRESSORS

Continuous function, microprocessor controlled, 3- way proportional Capacity Control Valve provides regulated output pressure independent of valve input pressure for a stable, smooth, and precise match of compres- sor capacity to cooling load to 10% of chiller capacity.

Automatic spring return of capacity control valve to minimum load position ensures compressor starting at minimum motor load. Internal discharge check to prevent rotor backspin upon shutdown.

Acoustically tuned, internal discharge gas path elimi- nates objectionable noise at the source, while optimiz- ing flow for maximum performance.

Reliable suction gas cooled, high efficiency, acces- sible hermetic motor with APT2000 type magnet wire and redundant overload protection using both ther- mistor and current overload protection.

Suction gas screen and serviceable, 0.5 micron full flow oil filter within the compressor housing.

Cast iron compressor housing precisely machined for optimal clearances and superb efficiency. Entire com- pressor, from suction to discharge has a Design Work- ing Pressure of 450psig (31 bar).

350W compressor body cartridge heater.

Each compressor will be mounted on isolator pads to reduce transmission of vibration to the rest of the unit.

COOLER

The dual-circuit cooler will be the direct-expansion type, with refrigerant in the tubes and chilled liquid flowing through the baffled shell. The design working pressure of the shell (liquid) side will be 150 PSIG (10.3 bar), and 300 PSIG (26.7 bar) for the tube (refrigerant) side.

The cooler will be constructed and tested in accordance with the applicable sections of the ASME Pressure Ves- sel Code, Section VlII, Division (1). The water side will be exempt per paragraph U-1, (c)(6).

The water baffles will be constructed of galvanized steel to resist corrosion. The removable heads will allow ac- cess to the internally enhanced, seamless, copper tubes. Vent and drain connections will be included.

The cooler will be covered with 3/4" (19.1 mm ) flexible, closed-cell, foam insulation (K = 0.25).

CONDENSER

The condenser is a cleanable thru-tube type with steel shell, copper tubes, removable water heads, and includes integral subcooling. Refer to PHYSICAL DATA for de- sign working pressures. The shell will be constructed and tested in accordance with section Vll, division 1 of the ASME pressure-vessel code. The water side is ex- empt per paragraph U-1 (c) of section VlII, division 1 of the ASME pressure-vessel code. The condenser is equipped with relief valves and will hold the full refriger- ant charge for pumpdown.

REFRIGERANT CIRCUIT

Two independent refrigerant circuits will be furnished on each unit. All piping will be copper with brazed joints. The liquid line will include: a shutoff valve with charging port; sightglass with moisture indicator; thermal expan- sion valve; solenoid valve; and high-absorption remov- able-core filter drier. The entire suction line and the liq- uid line between the expansion valve and the cooler will be insulated with flexible, closed-cell, foam insulation.

POWER AND CONTROL PANELS

All controls and motor starting equipment necessary for unit operation shall be factory wired and function tested. The panel enclosures shall be designed to NEMA 1 (IP

32)and manufactured from powder-painted galvanized steel.