York YCWS manual MULTIPOINT WIRING SYSTEM #2

Models: YCWS

1 52
Download 52 pages 28.43 Kb
Page 41
Image 41
MULTIPOINT WIRING SYSTEM #2

 

 

 

 

 

 

 

 

 

FORM 201.24-EG1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MULTIPOINT WIRING SYSTEM #2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHILLER

VOLT

TERM

TERMINAL BLK

N-F DIS

N-F DIS SW

 

CKT.BRKER

 

CUSTOMER

CUSTOMER

CKT.BRKR

CUSTOMER

 

 

MODEL

CODE

BLK

SW

 

 

GROUND

GROUND

 

GROUND

 

 

 

 

 

 

 

 

 

YCWS0100SC

 

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

#6 - 350 KCM

# 6 - 1/0 AWG

 

YCWS0120SC

 

#2/0 - 500 KCM

# 4 - 3/0 AWG

#6 - 350 KCM

# 6 - 1/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

 

YCWS0140SC

 

#2/0 - 500 KCM

# 4 - 3/0 AWG

#6 - 350 KCM

# 6 - 1/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

 

YCWS0180SC

-17

#2/0 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

 

YCWS0200SC

 

#2/0 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

 

YCWS0220SC

 

(2) #2 - 4/0 AWG

(2) # 6 - 1/0 AWG

(2) #3/0 - 250 KCM

# 4 - 3/0 AWG

(3) 2/0 - 400 KCM

(2) # 2 - 4/0 AWG

 

YCWS0240SC

 

(2) #2 - 4/0 AWG

(2) # 6 - 1/0 AWG

(2) #3/0 - 250 KCM

# 4 - 3/0 AWG

(3) 2/0 - 400 KCM

(2) # 2 - 4/0 AWG

 

 

YCWS0100SC

 

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

 

YCWS0120SC

 

#2 - 300 KCM

# 6 - 1/0 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

#4 - 300 KCM

# 4 - 3/0 AWG

 

YCWS0140SC

 

#2 - 300 KCM

# 6 - 1/0 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

#4 - 300 KCM

# 4 - 3/0 AWG

 

YCWS0180SC

-28

#2/0 - 500 KCM

# 4 - 3/0 AWG

#6 - 350 KCM

# 6 - 1/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

 

YCWS0200SC

 

#2/0 - 500 KCM

# 4 - 3/0 AWG

#6 - 350 KCM

# 6 - 1/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

 

YCWS0220SC

 

#2/0 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

 

YCWS0240SC

 

#2/0 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

 

 

YCWS0100SC

 

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

 

YCWS0120SC

 

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

 

YCWS0140SC

 

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

 

YCWS0180SC

-40

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

 

YCWS0200SC

 

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

 

YCWS0220SC

 

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

#6 - 350 KCM

# 6 - 1/0 AWG

 

YCWS0240SC

 

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

#6 - 350 KCM

# 6 - 1/0 AWG

 

 

YCWS0100SC

 

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

 

YCWS0120SC

 

#6 - 1/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

 

YCWS0140SC

 

#6 - 1/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

 

YCWS0180SC

-46

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

 

YCWS0200SC

 

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

 

YCWS0220SC

 

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

 

YCWS0240SC

 

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

 

 

YCWS0100SC

 

#18 - 2 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

 

YCWS0120SC

 

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#2 - 4/0 AWG

# 8 - 2 AWG

 

YCWS0140SC

 

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#2 - 4/0 AWG

# 8 - 2 AWG

 

YCWS0180SC

-58

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

 

YCWS0200SC

 

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

 

YCWS0220SC

 

#6 - 1/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#6 - 350 KCM

# 6 - 1/0 AWG

 

YCWS0240SC

 

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#6 - 350 KCM

# 6 - 1/0 AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

5.Circuit breakers supplied by third party vendors must be certified by local electrical standards. Maximum size is based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit.

6.The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per phase of the wire range specified. Actual wire size and number of wires per phase must be determined based on the National Electrical Code, using copper connectors only. Field wiring must also comply with local codes.

7.A ground lug is provided for each compressor system to accommodate a field grounding conductor per N.E.C. Table 250-95. A control circuit grounding lug is also supplied.

8.The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100, and is intended for isolating the unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.

9.Field Wiring by others which complies to the National Electrical Code & Local Codes.

YORK INTERNATIONAL

41

Page 41
Image 41
York YCWS manual MULTIPOINT WIRING SYSTEM #2