SAMPLE SELECTION

FORM 201.24-EG1

SAMPLE SELECTION

Water Cooled Condenser (YCWS)

GIVEN – Chill 200 GPM of water from 56ºF to 44ºF and 0.0001 evaporator fouling factor with 85ºF to 95ºF con- densing water available. Fouling factor of 0.0005 spe- cial field for the condenser.

FIND – The required unit size capacity, kW, EER, and water pressure drop.

SOLUTION:

1.Chilled water range = 56ºF - 44ºF = 12ºF and correc- tion factors are 1.0133 for Tons and 0.9993 for kW for the cooler.

2. Capacity (tons) =

GPM x Chilled Water Range

 

24

 

 

 

=

200 x 12

= 100TR

 

24

 

 

 

2.From the rating, a model YCWS0120SC has a ca- pacity range required. For the cooler leaving water temperature of 44ºF and a condenser leaving water temperature of 95ºF, the unit capacity rating table in- dicates:

Tons = 110.3

KW = 86.2

EER = 15.4

Correcting for the 12ºF chilled water range and the 0.0005 condenser-fouling factor:

Tons

= 110.3 x 1.0133 x 0.9961 = 111.3TR

KW

= 86.2 x 0.9993 x 1.0065 = 86.7

The unit is suitable.

3.Determine the average full load kW and EER at 95.0 Tons

95.0X (86.7) = 74KW

111.3

EER =

Tons x 12

= 95.0 X 12 = 15.4

Kw

74

 

4. Determine the cond. Heat rejection as follows:

Heat Rejection (MBH) = (Tons x 12) + (kW x 3.415)

=(95.0 x 12) + (74 x 3.415)

=1140 + 253

=1393

5.Determine GPM condensing water as follows:

MBH x2

GPM Condenser Water = Cond Water Range

6.From curves on pages 10 and 11, the pressure drops with 200GPM through the cooler and 288 through the condenser of the Model YCWS120SC

Cooler Pressure Drop at 200 GPM = 2.9ft Condenser Pressure Drop at 288 GPM = 5.5ft