Specifications (Continued)
override for servicing. | via the standard onboard RS485 communication port. |
Print - Operating data or system fault shutdown history | This Option also provides open system compatibility |
for last six faults. Printouts through an | with other communications networks (BACnet™ & |
separate printer (by others). | LONMARK™ via interface through standard onboard |
Program - | 485 or 232 port and an external YorkTalk Translator. |
• Low leaving liquid temperature cutout, 300 to 600 |
|
second | • Additional functions (password protected) for program- |
delay, and average motor current unload point. Liq- | ming by a qualified service technician: |
uid temperature setpoint reset signal from YORK ISN |
|
or building automation system (by others) via: | Cutouts for low suction pressure, high discharge |
• Pulse width modulated (PWM) input for up to 40°F | pressure, high oil temperature. |
| |
(22°C) total reset as standard. | Refrigerant type. |
• Optional Building Automation System interface input | High discharge pressure unload setpoint. |
card for up to 20°F (11.1°C) reset using a: 4 to 20 |
|
mA, 0 to 10 Vdc input, or discrete reset input. | Compressor motor current percent limit. |
• NOTE: The Standard MicroPanel can be directly con- |
|
nected to a YORK ISN Building Automation System |
|
6 | YORK INTERNATIONAL |