York YCWS manual Design Parameters, English

Models: YCWS

1 52
Download 52 pages 28.43 Kb
Page 8
Image 8
Design Parameters

Design Parameters

English

YCWS

0100SC

0120SC

0140SC

0180SC

0200SC

0220SC

0240SC

 

 

 

 

 

 

 

 

Min. Cooler Water Flow - GPM

200

200

200

260

260

300

300

Max. Cooler Water Flow - GPM

506

506

506

695

695

830

830

Min. Cond. Water Flow - GPM

193

193

193

330

330

330

330

Max. Cond. Water Flow - GPM

645

645

645

1050

1050

1050

1050

Min. Lvg. Liquid Temp. - °F

40

40

40

40

40

40

40

Max. Lvg. Liquid Temp. - °F

50

50

50

50

50

50

50

Min. Ent. Cond. Water Temp - °F

75

75

75

75

75

75

75

Max. Ent. Cond. Water Temp - °F

95

95

95

95

95

95

95

Min. Equipment Room Temp. - °F

40

40

40

40

40

40

40

Max. Equipment Room Temp. - °F

115

115

115

115

115

115

115

SI

YCWS

0100SC

0120SC

0140SC

0180SC

0200SC

0220SC

0240SC

 

 

 

 

 

 

 

 

Min. Cooler Water Flow - l/sec

12.6

12.6

12.6

16.4

16.4

18.9

18.9

Max. Cooler Water Flow - l/sec

31.9

31.9

31.9

43.8

43.8

52.4

52.4

Min. Cond. Water Flow - l/sec

12.2

12.2

12.2

20.8

20.8

20.8

20.8

Max. Cond. Water Flow - l/sec

40.7

40.7

40.7

66.2

66.2

66.2

66.2

Min. Lvg. Liquid Temp. - °C

4.4

4.4

4.4

4.4

4.4

4.4

4.4

Max. Lvg. Liquid Temp. - °C

10.0

10.0

10.0

10.0

10.0

10.0

10.0

Min. Ent. Cond. Water Temp - °C

23.8

23.8

23.8

23.8

23.8

23.8

23.8

Max. Ent. Cond. Water Temp - °C

35..0

35..0

35..0

35..0

35..0

35..0

35..0

Min. Equipment Room Temp. - °C

4.4

4.4

4.4

4.4

4.4

4.4

4.4

Max. Equipment Room Temp. - °C

46.1

46.1

46.1

46.1

46.1

46.1

46.1

8

YORK INTERNATIONAL

Page 8
Image 8
York YCWS manual Design Parameters, English