571209-YTG-C-1012

Physical and Electrical Data

MODEL

 

YHJD18

YHJD24

YHJD30

 

YHJD36

 

YHJD42

YHJD48

YHJD60

 

S41S2

S41S4

S41S4

 

S41S4

 

S41S4

S41S4

S41S5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Supply Voltage

 

 

 

 

208-230V, 1φ, 60Hz

 

 

 

Normal Voltage Range 1

 

 

 

 

187 to 252

 

 

 

Minimum Circuit Ampacity

11.9

11.2

14.1

19.7

 

20.9

25.6

42.6

 

 

 

 

 

 

 

 

 

Max. Overcurrent Device Amps 2

20

15

20

30

 

35

45

70

Min. Overcurrent Device Amps 3

15

15

15

20

 

25

30

45

Compressor Type

 

Scroll

Recip

Recip

 

Recip

Recip

Recip

Scroll

 

 

 

 

 

 

 

 

 

 

Compressor Amps

Rated Load

9.0

8.3

10.6

14.7

 

15.7

19.4

33.0

Locked Rotor

48.0

43.0

54.0

74.0

 

88.0

88.0

134.0

 

 

 

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

No

Yes

Yes

 

Yes

Yes

Yes

No

 

 

 

 

 

 

 

 

 

Factory External Discharge Muffler

Yes

No

No

 

No

No

No

Yes

 

 

 

 

 

 

 

 

 

Factory External Check Valve

No

No

No

 

No

No

No

No

 

 

 

 

 

 

 

 

 

HS Kit Required with TXV 4

No

Yes

Yes

 

Yes

Yes

Yes*

No

Fan Motor Amps

Rated Load

0.70

0.80

0.80

1.3

 

1.3

1.3

1.5

Fan Diameter Inches

 

24

24

24

24

 

24

24

24

 

Rated HP

1/10

1/8

1/8

1/4

 

1/4

1/4

1/4

Fan Motor

Nominal RPM

825

1075

1075

850

 

850

850

850

 

Nominal CFM

2000

2900

3000

3800

 

3800

3600

3550

 

Face Area Sq. Ft.

15.7

18.3

21.0

23.6

 

23.6

23.6

23.6

Coil

Rows Deep

1

1

1

1

 

1

2

2

 

Fins / Inch

22

22

22

22

 

22

18

18

Liquid Line Set OD

(Field Installed)

3/8

3/8

3/8

3/8

 

3/8

3/8

3/8

Vapor Line Set OD (Field Installed)

3/4

3/4

3/4

3/4

 

7/8

7/8

1-1/8

Unit Charge (Lbs. - Oz.) 5

6 - 6

9 - 6

9 - 0

10 - 0

 

9 - 10

14 - 12

15 - 0

Charge Per Foot, Oz.

0.62

0.62

0.62

0.62

 

0.67

0.67

.76

Operating Weight Lbs.

172

194

206

218

 

218

285

290

*These models are shipped with a Hard Start Kit installed at the factory.

1.Rated in accordance with AHRI Standard 110-2012, utilization range “A”.

2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.

4.See Hard Start Kit Accessory Installation Manual for Hard Start Kit part number for each model.

5.The Unit Charge is correct for the outdoor unit, smallest matched indoor unit, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

C

A

B

2

Unit

 

Dimensions

 

Refrigerant Connection

 

 

(Inches)

 

Service Valve Size

Model

 

 

 

 

 

 

 

 

 

 

A

 

B

 

C

Liquid

Vapor

 

 

 

 

 

 

 

 

 

 

 

18

28-1/4

 

34

 

34

 

 

 

 

 

 

 

 

 

 

24

32-1/4

 

34

 

34

 

3/4

 

 

 

 

 

 

 

30

36-1/4

 

34

 

34

 

 

 

 

 

 

 

 

 

 

 

3/8

 

36

40-1/4

 

34

 

34

 

 

 

 

 

 

 

 

 

42

40-1/4

 

34

 

34

 

7/8

 

 

 

 

 

 

 

48

40-1/4

 

34

 

34

 

 

 

 

 

 

 

 

 

 

 

 

 

60

40-1/4

 

34

 

34

 

7/8*

 

 

 

 

 

 

 

 

* Adapter fitting required for 1-1/8" line set.

All dimensions are in inches and are subject to change without notice. Overall height is from bottom of base pan to top of fan guard.

Overall length and width include screw heads.

Johnson Controls Unitary Products

Page 2
Image 2
York YHJD18 THRU 60 warranty Physical and Electrical Data, Model