571209-YTG-C-1012
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJD48S41S4 |
|
|
|
|
|
|
|
|
|
|
|
| ||||
INDOOR COIL MODEL NO. | AHP48 |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
CONDENSING | IDCFM |
|
| 1510 |
|
|
|
| 1710 |
|
|
|
| 1910 |
|
|
ENTERING AIR | ID DB (°F) | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 |
TEMPERATURE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ID WB (°F) | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
| T.C. | 47.6 | 50.1 | 49.8 | 54.1 | 60.7 | 49.4 | 50.8 | 51.0 | 55.8 | 61.9 | 51.2 | 51.5 | 52.2 | 57.5 | 63.1 |
65 | S.C. | 47.6 | 44.7 | 37.8 | 37.0 | 30.4 | 49.4 | 48.3 | 39.9 | 39.3 | 31.5 | 51.2 | 51.5 | 42.0 | 41.6 | 32.6 |
| KW | 2.90 | 2.90 | 2.90 | 3.00 | 3.00 | 3.00 | 3.00 | 3.00 | 3.00 | 3.10 | 3.10 | 3.10 | 3.10 | 3.10 | 3.20 |
| T.C. | 45.1 | 46.6 | 46.5 | 50.8 | 56.9 | 46.7 | 47.2 | 47.5 | 52.2 | 58.0 | 48.4 | 47.9 | 48.5 | 53.6 | 59.0 |
75 | S.C. | 45.1 | 43.1 | 36.2 | 35.6 | 28.9 | 46.7 | 45.8 | 38.3 | 37.8 | 30.0 | 48.4 | 47.9 | 40.3 | 40.0 | 31.1 |
| KW | 3.20 | 3.20 | 3.20 | 3.20 | 3.30 | 3.20 | 3.20 | 3.20 | 3.30 | 3.30 | 3.30 | 3.30 | 3.30 | 3.40 | 3.40 |
| T.C. | 42.5 | 43.1 | 43.2 | 47.5 | 53.2 | 44.1 | 43.7 | 44.0 | 48.6 | 54.1 | 45.6 | 44.3 | 44.7 | 49.7 | 55.0 |
85 | S.C. | 42.5 | 41.5 | 34.7 | 34.2 | 27.3 | 44.1 | 43.3 | 36.7 | 36.2 | 28.4 | 45.6 | 44.3 | 38.7 | 38.3 | 29.6 |
| KW | 3.40 | 3.40 | 3.40 | 3.50 | 3.50 | 3.50 | 3.50 | 3.50 | 3.50 | 3.60 | 3.60 | 3.60 | 3.60 | 3.60 | 3.70 |
| T.C. | 40.0 | 39.6 | 39.9 | 44.2 | 49.4 | 41.4 | 40.2 | 40.4 | 45.0 | 50.2 | 42.8 | 40.7 | 41.0 | 45.8 | 51.0 |
95 | S.C. | 40.0 | 39.6 | 33.1 | 32.7 | 25.8 | 41.4 | 40.2 | 35.0 | 34.7 | 26.9 | 42.8 | 40.7 | 37.0 | 36.6 | 28.0 |
| KW | 3.60 | 3.60 | 3.60 | 3.70 | 3.80 | 3.70 | 3.70 | 3.70 | 3.80 | 3.90 | 3.80 | 3.80 | 3.80 | 3.90 | 4.00 |
| T.C. | 37.2 | 37.1 | 36.3 | 40.6 | 45.3 | 38.5 | 37.8 | 36.8 | 41.1 | 45.9 | 39.7 | 38.6 | 37.2 | 41.7 | 46.6 |
105 | S.C. | 37.2 | 37.1 | 31.6 | 31.3 | 24.2 | 38.5 | 37.8 | 33.5 | 33.2 | 25.2 | 39.7 | 38.6 | 35.4 | 35.1 | 26.3 |
| KW | 3.90 | 3.90 | 3.90 | 4.00 | 4.10 | 4.00 | 4.00 | 3.90 | 4.00 | 4.20 | 4.10 | 4.10 | 4.00 | 4.10 | 4.20 |
| T.C. | 34.5 | 34.5 | 32.8 | 36.9 | 41.1 | 35.5 | 35.5 | 33.1 | 37.2 | 41.6 | 36.6 | 36.4 | 33.5 | 37.6 | 42.1 |
115 | S.C. | 34.5 | 34.5 | 30.0 | 29.8 | 22.5 | 35.5 | 35.5 | 31.9 | 31.7 | 23.6 | 36.6 | 36.4 | 33.5 | 33.5 | 24.6 |
| KW | 4.10 | 4.10 | 4.10 | 4.20 | 4.30 | 4.20 | 4.20 | 4.20 | 4.30 | 4.40 | 4.40 | 4.40 | 4.30 | 4.40 | 4.50 |
| T.C. | 31.7 | 31.9 | 29.3 | 33.2 | 37.0 | 32.6 | 33.1 | 29.5 | 33.3 | 37.3 | 33.5 | 34.2 | 29.7 | 33.4 | 37.7 |
125 | S.C. | 31.7 | 31.9 | 28.5 | 28.3 | 20.9 | 32.6 | 33.1 | 29.5 | 30.1 | 21.9 | 33.5 | 34.2 | 29.7 | 31.9 | 22.9 |
| KW | 4.40 | 4.40 | 4.30 | 4.50 | 4.60 | 4.50 | 4.50 | 4.40 | 4.50 | 4.70 | 4.60 | 4.60 | 4.50 | 4.60 | 4.80 |
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between
Air Handlers | Coils | T.C. | S.C. | KW |
– | FC/MC/PC60 | 0.98 | 0.97 | 0.98 |
– | FC/MC62 | 0.99 | 0.98 | 0.98 |
– | UC60 | 0.97 | 0.95 | 0.97 |
AHE48D | – | 0.99 | 0.97 | 0.93 |
AHE60D | – | 1.00 | 0.99 | 0.92 |
AHR48D | – | 0.98 | 0.95 | 0.98 |
AHR60D | – | 0.98 | 0.97 | 0.97 |
AHV48D | – | 0.99 | 0.96 | 0.94 |
AHV60D | – | 0.99 | 0.99 | 0.94 |
AV*48 | – | 0.99 | 0.99 | 0.93 |
AV*60 | – | 1.00 | 0.99 | 0.93 |
MV16C | FC60C | 0.99 | 0.99 | 0.94 |
MV20D | FC/MC60D | 0.99 | 0.99 | 0.94 |
MV20D | FC/MC62D | 1.00 | 0.99 | 0.93 |
MX16C | FC60C | 1.00 | 0.99 | 0.92 |
MX20D | FC/MC60D | 1.00 | 1.00 | 0.91 |
MX20D | FC/MC62D | 1.01 | 1.00 | 0.91 |
Continued on next page.
Johnson Controls Unitary Products | 33 |