York YHJD18 THRU 60 warranty HEATING CAPACITY - With Air Handler Continued

Models: YHJD18 THRU 60

1 44
Download 44 pages 33.26 Kb
Page 14
Image 14

571209-YTG-C-1012

HEATING CAPACITY - With Air Handler (Continued)

UNIT

AIR

COIL1

 

 

 

HEATING2

 

 

 

MODEL

HANDLER

MODEL

 

47 °F

 

 

 

 

17 °F

 

HSPF

 

 

 

MBH

COP

KW

 

MBH

 

COP

KW

STD

 

 

13 SEER HP WITH AIR HANDLERS

 

 

 

 

 

 

 

 

AHE48D

39.0

3.90

3.00

 

21.8

 

2.64

2.52

8.20

 

AHR48D

40.0

3.66

3.20

 

22.4

 

2.48

2.65

7.70

 

AHV48D

39.5

3.86

3.00

 

21.0

 

2.54

2.42

8.20

 

AV*48

39.5

3.96

2.92

 

22.2

 

2.68

2.43

8.20

YHJD42S41S4

AV*60

39.5

3.98

2.91

 

22.2

 

2.70

2.41

8.20

 

MV16C

FC60C

40.0

3.86

3.04

 

21.4

 

2.50

2.51

8.20

 

MV20D

FC/MC60D

39.5

3.94

2.94

 

22.2

 

2.66

2.45

8.20

 

MX16C

FC60C

40.0

4.08

2.87

 

22.0

 

2.66

2.42

8.20

 

MX20D

FC/MC60D

40.0

4.10

2.86

 

21.8

 

2.68

2.38

8.20

 

AHE48D

45.5

3.68

3.62

 

26.8

 

2.84

2.76

8.20

 

AHE60D

44.5

3.72

3.50

 

26.4

 

2.90

2.67

8.20

 

AHR48D

46.0

3.56

3.79

 

27.4

 

2.74

2.93

7.70

 

AHR60D

45.5

3.52

3.79

 

27.2

 

2.74

2.91

7.75

 

AHV48D

44.5

3.56

3.66

 

26.4

 

2.78

2.78

8.20

 

AHV60D

45.0

3.62

3.64

 

26.8

 

2.82

2.78

8.20

YHJD48S41S4

AV*48

46.0

3.78

3.57

 

26.8

 

2.90

2.71

8.20

AV*60

45.5

3.80

3.51

 

26.8

 

2.94

2.67

8.20

 

 

 

 

MV16C

FC60C

45.0

3.70

3.56

 

26.6

 

2.90

2.69

8.20

 

MV20D

FC/MC60D

45.5

3.72

3.58

 

27.0

 

2.86

2.77

8.20

 

MV20D

FC/MC62D

45.0

3.72

3.54

 

26.6

 

2.90

2.69

8.20

 

 

 

 

 

 

 

 

 

 

 

 

 

MX16C

FC60C

45.0

3.80

3.47

 

26.2

 

2.96

2.59

8.20

 

 

 

 

 

 

 

 

 

 

 

 

 

MX20D

FC/MC60D

45.5

3.84

3.47

 

26.6

 

2.94

2.65

8.20

 

 

 

 

 

 

 

 

 

 

 

 

 

MX20D

FC/MC62D

45.5

3.80

3.51

 

26.4

 

2.94

2.63

8.20

 

AHE60D

58.0

3.54

5.01

 

39.0

 

2.76

4.14

8.20

 

AHR60D

58.0

3.44

5.28

 

40.0

 

2.68

4.37

8.15

 

 

 

 

 

 

 

 

 

 

 

 

 

AHV60D

58.0

3.42

5.18

 

39.0

 

2.68

4.26

8.15

YHJD60S41S5

 

 

 

 

 

 

 

 

 

 

 

MV20D

FC/MC62D

58.0

3.52

5.08

 

39.0

 

2.72

4.20

8.20

 

 

 

 

 

 

 

 

 

 

 

 

 

MV20D

FC64D

58.0

3.40

5.34

 

40.5

 

2.80

4.24

8.10

 

 

 

 

 

 

 

 

 

 

 

 

 

MX20D

FC/MC62D

58.0

3.58

4.95

 

38.5

 

2.76

4.09

8.20

 

 

 

 

 

 

 

 

 

 

 

 

 

MX20D

FC64D

58.0

3.44

5.20

 

40.0

 

2.86

4.10

8.15

1.Rated CFM same as for cooling.

2.Heating MBH based on AHRI standards of 70 °F DB (Dry Bulb) entering indoor air, 72% RH (Relative Humidity) outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation.

COP equals MBH output divided by (total KW input x 3.412).

HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period.

MA Modular Air Handlers use Coil Only Ratings.

— = Not Applicable.

14

Johnson Controls Unitary Products

Page 14
Image 14
York YHJD18 THRU 60 warranty HEATING CAPACITY - With Air Handler Continued