York YHJD18 THRU 60 warranty System Charge for Various Matched Systems, Procedures

Models: YHJD18 THRU 60

1 44
Download 44 pages 33.26 Kb
Page 3
Image 3
System Charge for Various Matched Systems

571209-YTG-C-1012

System Charge for Various Matched Systems

Outdoor Unit

YHJD18S41S2

YHJD24S41S4

YHJD30S41S4

YHJD36S41S4

YHJD42S41S4

YHJD48S41S4

YHJD60S41S5

Required Orifice or TXV 1,2

.051/4F1

.054, .059/4G1

.063/4G1

.071/4H1

.075/4H1

4J1

4K1

 

 

 

 

 

 

Indoor Unit 3,4,5

 

 

Additional Charge, Oz

 

 

AHE18B

.051/ TXV + 0

AHE24B

.054 / TXV + 0

AHE30B

.054 / TXV + 0

.063 / TXV + 0

AHE36C

.063 / TXV + 25

.071 / TXV + 0

AHE42D

.071 / TXV + 16

AHE48D

.075 / TXV + 0

TXV + 0

AHE60D

TXV + 25

TXV + 0

AHR18B

.051/ TXV + 0

AHR24B

.054 / TXV + 0

AHR30B

.063 / TXV + 0

AHR36B

.063 / TXV + 25

.071 / TXV + 6

AHR42C

.071 / TXV + 16

AHR48D

.075 / TXV + 0

TXV + 0

AHR60D

TXV + 25

TXV + 0

AHV18B

.051/ TXV + 0

AHV24B

.054 / TXV + 0

AHV30B

.054 / TXV + 0

.063 / TXV + 0

AHV36C

.059 / TXV + 23 .063 / TXV + 25

.071 / TXV + 6

AHV42D

.071 / TXV + 16

AHV48D

.075 / TXV + 0

TXV + 0

AHV60D

TXV + 25

TXV + 0

AV*24

.051/ TXV + 3

AV*36

.059 / TXV + 23 .063 / TXV + 25

.071 / TXV + 6

AV*48

.075 / TXV + 0

TXV + 0

AV*60

.075 / TXV + 0

TXV + 0

FC/MC/PC18

.051/ TXV + 0

FC/MC/PC24

.051/ TXV + 5

FC/MC/PC30

.051/ TXV + 5

FC/MC/PC32

.059 / TXV + 0

.063 / TXV + 0

FC/MC/PC35

.059 / TXV + 0

.063 / TXV + 0

FC/MC/PC37

.059 / TXV + 23 .063 / TXV + 25

.071 / TXV + 6

FC/MC/PC43

.059 / TXV + 23 .063 / TXV + 25

.071 / TXV + 6

FC/MC/PC/UC48

.071 / TXV + 16

FC/MC/PC/UC60

.075 / TXV + 0

TXV + 0

FC/MC62

TXV + 25

TXV + 0

FC64

TXV + 23

UC18

.051/ TXV + 1

UC24

.051/ TXV + 7

UC30

.051/ TXV + 7

UC48

.071 / TXV + 25

UC60

.075 / TXV + 2

TXV + 11

Some of the combinations shown in the above System Charge table require Advanced Main Air Circulating Fan indoor product. For approved coil only matches, please see the “COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils” table.

FOOTNOTES:

1.For applications requiring a TXV use S1-1TVM*** series kit.

2.Approved orifice(s) shipped with outdoor unit.

3.Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower Time Delay Kit S1-2FD06700224.

4.PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.

5.Refer to Cooling and Heating Performance Data tables for actual performance for specified system matches.

PROCEDURES:

1.Unit factory charge listed on the unit nameplate includes refrigerant for the outdoor unit, the smallest matched indoor unit, and 15 feet of interconnecting line tubing.

2.Verify the TXV or orifice and additional charge required for specific matched indoor unit in the system using the above table.

3.Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.

4.For indoor matches requiring additional charge, the refrigerant needs to be weighed in for specific matched indoor unit and lineset length.

5.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + charge adder for matched indoor unit + charge adder for line set.