571209-YTG-C-1012

COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils (Coil Only Ratings)

 

COIL

 

 

CFM RANGE

 

 

 

COOLING

 

 

UNIT MODEL

 

 

 

RATED

 

NET MBH

SEER1

 

MODEL

WIDTH

 

(Min.-max.)

 

EER

 

 

CFM

 

 

 

 

 

 

TOTAL

SENS.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13 SEER HP COIL

ONLY RATINGS

 

 

 

 

 

 

FC/MC/PC18

14.5,17.5

 

450

- 750

600

 

18.0

14.0

13.00

11.00

 

FC/MC/PC24

14.5,17.5

 

450

- 750

600

 

18.0

14.0

13.50

11.00

YHJD18S41S2

FC/MC/PC30

14.5,17.5

 

450

- 750

600

 

18.0

13.7

13.00

11.00

 

UC24

14.5,17.5

 

450

- 750

600

 

18.0

13.8

13.05

11.00

 

UC30

14.5,17.5

 

450

- 750

600

 

18.0

13.8

13.05

11.00

 

FC/MC/PC32

14.5

 

600 - 1000

800

 

23.8

17.1

13.00

11.00

YHJD24S41S4

FC/MC/PC35

17.5,21.0

 

600 - 1000

800

 

23.6

17.1

13.00

11.00

FC/MC/PC37

14.5

 

600 - 1000

800

 

24.0

17.3

13.00

11.00

 

 

 

 

FC/MC/PC43

17.5,21.0

 

600 - 1000

800

 

24.0

17.3

13.00

11.00

 

FC/MC/PC32

14.5

 

800 - 1200

1000

 

29.8

21.8

13.00

11.00

YHJD30S41S4

FC/MC/PC35

17.5,21.0

 

800 - 1200

1000

 

29.8

21.8

13.00

11.00

FC/MC/PC37

14.5

 

800 - 1200

1000

 

30.0

22.2

13.00

11.00

 

 

 

 

FC/MC/PC43

17.5,21.0

 

800 - 1200

1000

 

30.0

22.2

13.00

11.00

 

FC/MC/PC37

14.5

 

1000

- 1400

1200

 

36.0

26.8

13.00

11.00

YHJD36S41S4

FC/MC/PC43

17.5,21.0

 

1000

- 1400

1200

 

36.0

26.6

13.00

11.00

FC/MC/PC48

21.0,24.5

 

1000

- 1400

1200

 

36.0

26.6

13.00

11.00

 

 

 

 

UC48

21.0,24.5

 

1000

- 1400

1200

 

36.0

26.8

13.00

11.00

YHJD42S41S4

FC/MC/PC60

21.0,24.5

 

1200

- 1600

1400

 

41.0

31.8

13.00

11.00

UC60

21.0,24.5

 

1200

- 1600

1400

 

40.5

31.0

13.00

11.00

 

 

 

 

FC/MC/PC60

21.0,24.5

 

1400

- 1800

1600

 

44.0

33.4

13.00

11.00

YHJD48S41S4

FC/MC62

24.5

 

1400

- 1800

1600

 

44.5

33.8

13.00

11.00

 

UC60

21.0,24.5

 

1400

- 1800

1600

 

44.0

32.8

13.00

11.00

YHJD60S41S5

FC/MC62

24.5

 

1600

- 2000

1800

 

57.5

41.0

13.25

11.35

FC64

24.5

 

1600

- 2000

1800

 

56.5

42.5

13.00

11.00

 

 

 

1.Requires a S1-2FD06700224 Blower Time Delay unless a standard furnace is equipped with one.

MA Modular Air Handlers use Coil Only Ratings.

PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Ratings.

COOLING CAPACITY - With High Efficiency Motor Furnaces

UNIT

FURNACE

COIL

 

 

COOLING

 

 

 

 

 

RATED

Net MBH

 

 

MODEL

MODEL

 

WIDTH

MODEL1

SEER

EER

 

CFM

TOTAL

SENS.

 

 

 

 

 

 

 

 

 

13 SEER HP WITH HIGH EFFICIENCY MOTOR FURNACES2

 

 

 

 

T*(8,L)V*A12

14.5

FC/MC/PC18A

620

18.0

12.3

14.50

12.30

 

 

 

 

 

 

 

 

 

 

T*(8,L)V*A12

14.5

FC/MC/PC24A

640

18.0

12.7

14.80

12.50

 

 

 

 

 

 

 

 

 

 

T*(8,L)V*A12

14.5

FC/MC/PC30A

640

18.0

12.7

14.80

12.50

 

 

 

 

 

 

 

 

 

 

T*(8,L)V*A12

14.5

UC18A

620

18.0

12.4

14.60

12.30

 

 

 

 

 

 

 

 

 

 

T*(8,L)V*A12

14.5

UC24A

640

18.0

12.8

14.80

12.50

 

 

 

 

 

 

 

 

 

 

T*(8,L)V*A12

14.5

UC30A

640

18.0

12.8

14.80

12.50

 

 

 

 

 

 

 

 

 

 

T*(8,L)V*B12

14.5

FC/MC/PC18A

620

18.0

12.3

14.50

12.30

 

 

 

 

 

 

 

 

 

YHJD18S41S2

T*(8,L)V*B12

17.5

FC/MC/PC24B

575

18.0

12.2

14.90

12.60

 

 

 

 

 

 

 

 

 

T*(8,L)V*B12

17.5

FC/MC/PC30B

575

18.0

12.2

14.90

12.60

 

 

 

 

 

 

 

 

 

 

 

T*(8,L)V*B12

17.5

UC18B

580

18.0

12.0

14.60

12.30

 

 

 

 

 

 

 

 

 

 

T*(8,L)V*B12

17.5

UC24B

575

18.0

12.3

14.90

12.60

 

 

 

 

 

 

 

 

 

 

T*(8,L)V*B12

17.5

UC30B

575

18.0

12.3

15.00

12.60

 

 

 

 

 

 

 

 

 

 

T*(8,L)X*A12

14.5

FC/MC/PC18A

540

18.0

14.3

14.00

12.00

 

 

 

 

 

 

 

 

 

 

T*(8,L)X*A12

14.5

FC/MC/PC24A

595

18.0

14.9

14.00

12.00

 

 

 

 

 

 

 

 

 

 

T*(8,L)X*A12

14.5

FC/MC/PC30A

595

18.0

14.9

14.00

12.00

 

 

 

 

 

 

 

 

 

 

T*(8,L)X*A12

14.5

UC18B

590

18.0

13.9

14.50

12.00

For Notes See Page 12.