Generac 005030-0 (15kW), 005031-0 (25kW) Battery Installation, ‹ 2.11.1 Vented Batteries

Page 15

Section 2 — Installation

Liquid-cooled 15, 20 and 25 kW Generators

Transfer Switch terminals N1 and N2 (also called Utility 1 and Utility 2) are the input utility AC power connections to the Transfer Switch. Transfer Switch terminals T1 and T2 (also called Load 1 and Load 2) are the transfer switch AC output power terminals that go to the load circuit distribution panel. Transfer Switch terminals E1 and E2 are the AC power termi- nals that come from the generator's main alternator.

When in GTS mode, the control board will respond as follows based on the generator AUTO/OFF/MANU- AL switch position.

OFF — The generator will not start and run in this position

MANUAL — The generator control board will start and run the generator whenever the switch is in the manual position.

AUTO — The generator control board will monitor the 2-Wire start circuit (terminals 178 and 183 in the generator control panel). When a 2-Wire start signal is issued by the W type engineered transfer switch, via a relay contact closure that connects wire 178 to wire 183, the generator control board will immedi- ately start and run the generator. When the 2-Wire start signal is removed the control board will imme- diately stop the generator.

2.11BATTERY INSTALLATION

DANGER

Standby generators installed with automatic ! transfer switches will crank and start automati-

cally when NORMAL (UTILITY) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to personnel, do not connect battery cables until certain that normal source voltage at the transfer switch is correct; the generator main line circuit breaker is switched to OFF; the AUTO/OFF/MANUAL switch on the control con- sole is switched to OFF; the 15A and 5A fuses have been removed from the control console; utility fed supply to battery charger (terminals

N1 and N2) is removed; and the system is ready to be placed into operation. Ensure that the 5A and 15A fuses in the control panel are removed when connecting or disconnecting battery cables.

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks or any spark producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely corro- ! sive sulfuric acid solution that can cause severe

burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.

Do not dispose of the battery in a fire. The bat- tery is capable of exploding.

Do not open or mutilate the battery. Released ! electrolyte can be toxic and harmful to the skin

and eyes.

The battery represents a risk of high short cir- cuit current. When working on the battery, always remove watches, rings or other metal objects, and only use tools that have insulated handles.

‹2.11.1 VENTED BATTERIES

The electrolyte is a dilute sulfuric acid that is

!harmful to the skin and eyes. It is electrically conductive and corrosive. The following proce- dures are to be observed:

Wear full eye protection and protective clothing,

Where electrolyte contacts the skin, wash it off immediately with water,

Where electrolyte contacts the eyes, flush thor- oughly and immediately with water and seek med- ical attention, and

Spilled electrolyte is to be washed down with an acid-neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbon- ate of soda to one gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.

Lead acid batteries present a risk of fire because they generate hydrogen gas. The fol- lowing procedure are to be followed:

DO NOT SMOKE when near batteries,

DO NOT cause flame or spark in battery area, and

Discharge static electricity from body before touch- ing batteries by first touching a grounded metal surface.

Servicing of batteries is to be performed or super- vised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized person- nel away from batteries.

13

Image 15
Contents This manual should remain with the unit Introduction Authorized Service Dealer Location‹ Operation and Maintenance ‹ HOW to Obtain ServiceTable of Contents General Hazards ‹ Standards Index Electrical HazardsGenerator Transfer SwitchAutomatic Transfer Switch ATS Mode Engineered Transfer Switch Wire Start GTS ModeGenerator Fuel System ‹ 1.8.1 LOW OIL Pressure Switch‹ 1.8.2 High Coolant Temperature Switch Main Circuit BreakerLifting the Generator UnpackingSpecifications Fuel ConsumptionAWSF-52-C Before Installation Coolant RecommendationsEngine OIL Recommendations ‹ 2.1.2 Other Published Standards Generator LocationGenerator Mounting Support ‹ 2.1.1 Nfpa StandardsEmergency Circuit Isolation Method Basic Standby Electric SystemTotal Circuit Isolation Method Grounding the GeneratorGenerator AC Neutral Connections Connection Diagram ATS ModeConnection Diagram GTS Mode ‹ 2.11.1 Vented Batteries Battery InstallationPreparation Before START-UP Manual Transfer START-UP Control Console ComponentsBat Red Oil Red Temp Red Speed Red Crank Red Engine Governor Gain AdjustmentsManual Retransfer Shutdown Automatic OperationWeekly Exercise Cycle Voltage Regulator Adjustment Control Board DIP Switch SettingsIntake Manifold Procedure Exhaust Manifold ProcedureChecking Fluid Levels Cylinder Head ProcedureCooling System Overload Protection for Engine DC Electrical System‹ 4.8.1 Check Engine OIL Level ‹ 4.7.2 Battery Fluid ‹ 4.8.6 Perform Visual Inspection‹ 4.8.2 Check Battery ‹ 4.7.3 Engine Coolant‹ 4.8.13 Coolant Change Miscellaneous Maintenance‹ 4.8.11 Changing the Engine AIR Cleaner ‹ 4.9.1 Cleaning the Generator‹ 4.9.3 Battery Maintenance ‹ 4.9.4 Battery ReplacementPeriodic Replacement Parts Service Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsLiquid-cooled 15, 20 and 25 kW Generators Liquid-cooled 15, 20 and 25 kW Generators Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Page Battery Post Cover Black Support Battery TrayHold Down Battery Assembly Battery TrayTo B Duct Discharge RH AL 2.5L Assy Wire 14AWG 7.5 #0 GRN/YELDoor Battery Compartment Duct Intake MID AL 2.5LPage TOP, Control Panel Switch ROC Dpst 125V SPDSwitch ROC Dpdt ON-OFF-ON Hang TAG 2 Wire Start not ShownPage Harness Ctrl PNL 2.5L Ford AL not Shown 13 17 NUT HEX M10-1.5 G8 YEL CHR Tank Coolant RecoveryEngine 2.5L Ford STARTER, 12 VoltTo Engine Bracket Fuel Regulator Body Carburetor AssemblyCover AIR Cleaner GASKET, AIR Cleaner AdapterLocktight Rotor 390 40KW 1P Direct HSB 3.9L Chrysler Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 390 25KW 1P Direct HSB 2.5L FordSaddle 2 Inch Pipe Muffler OUTPipe Exhaust 2.5L Ford Muffler 2.5L FordHarn GOV 2.5L Ford Housing Governor ConnectorCover Connector Housing ASM Motor StepperRadiator 2.5L Ford HOSE, 2.5L Ford LowerBarbed STR 1/4 NPT X 3/8 ALMInstallation Diagram Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyThis Warranty Shall not Apply to the Following

005030-0 (15kW), 005031-0 (25kW) specifications

Generac has long been recognized as a leader in backup power solutions, and its 005031-0 (25kW) and 005030-0 (15kW) home standby generators exemplify the brand's commitment to reliability and performance. Designed for residential use, these generators provide peace of mind during outages, ensuring that homes remain powered even in the most challenging conditions.

One of the standout features of both models is their advanced Generac G-Force engine, which is engineered for longevity and impressive power output. The G-Force engine is built from the ground up for generator use, refined to handle the unique demands of continuous operation. This results in a highly durable system that requires little to no maintenance, making it a favored choice for homeowners looking for a reliable energy solution.

Another important characteristic is the True Power technology featured in both generators. This technology delivers clean, stable power that is safe for sensitive electronics and appliances. It ensures that devices such as computers and medical equipment operate smoothly without the risk of damage from power fluctuations. Additionally, the Generac 005031-0 and 005030-0 generators are equipped with the Quiet-Test mode, allowing them to run at lower RPMs during routine weekly self-tests. This innovation significantly reduces the noise produced during tests, making it less disruptive for residents.

Furthermore, these generators come with a user-friendly interface and a mobile link app, enabling homeowners to monitor their generator's performance remotely via a smartphone. This feature enhances convenience, allowing users to receive alerts and notifications about their generator's status, maintenance needs, and operation conditions right from their devices.

Both the 25kW and 15kW models are also designed with a robust transfer switch, which seamlessly shifts power from the grid to the generator in case of any outages. This automatic transfer feature ensures that homes maintain power without needing manual intervention, making them ideal for those who want uninterrupted electricity.

In terms of fuel source, both models operate on natural gas or propane, providing flexibility to homeowners regarding fuel availability and preferences. With excellent warranty options and Generac's reputation for quality, both the 005031-0 (25kW) and 005030-0 (15kW) generators stand as dependable choices for safeguarding homes from the unpredictability of power outages.