Generac 005030-0 (15kW) Manual Retransfer Shutdown, Automatic Operation, Weekly Exercise Cycle

Page 19

Section 3 - Operation

Liquid-cooled 15, 20 and 25 kW Generators

6.Reduce load to 3/4, 1/2, 1/4 and no load. Decrease the stability pot if there is instability at any load point.

7.Adjust differential pot to make the recovery to load changes even faster and minimize load change undershoot and overshoot. If it is set too high, it may introduce oscillations at some load. It can be set to zero (full CCW) if a small amount causes oscillations at some load.

8.Leave DIP switch 8 in TEST mode.

1.Place the AUTO/OFF/MANUAL switch in the AUTO position (Figure 3.3).

2.Press and hold the “Set Exercise Time” switch for five seconds, then release.

At this time all five red LEDs will flash for approxi- mately 10 seconds, then the engine will start and run for it’s 12 minute exercise period, then shut down. The generator will now start and run each week at the same time.

3.4MANUAL RETRANSFER AND

SHUTDOWN

When utility power source voltage has been restored, electrical loads may be transferred back to that source and the generator can be shut down as fol- lows:

Verify that utility power supply voltage to the trans- fer switch has been positively turned Off, using whatever means provided (such as utility main line circuit breaker).

Set the generator’s main circuit breaker to its Off or Open position.

Let the generator engine run at no-load for a few minutes, to stabilize internal unit temperatures.

On the generator console, set the Auto/Off/ Manual switch to Off. Wait for engine to come to a complete stop.

For transfer to utility position, refer to the Owner’s Manual of the particular transfer switch.

Turn on the utility power supply to the transfer switch, using whatever means provided (such as a utility main line circuit breaker). The utility power source now powers the loads.

3.5AUTOMATIC OPERATION

To set the system for fully automatic operation, pro- ceed as follows:

Check that load circuits are connected to the utility power supply.

Set the AUTO/OFF/MANUAL switch to its AUTO position.

Set the generator main circuit breaker to its ON or CLOSED position.

Figure 3.3 - “Set Exercise Time” Switch

RED LED'S = INDIVIDUAL FAULT

(SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)

 

AUTO

OFF

 

 

OFF

ON

 

SET

MANUAL

EXERCISE

 

TIME

 

TO SET EXERCISER TIME

1)PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.

2)HOLD "SET EXERCISE TIME" SWITCH IN "ON" POSITION FOR THREE SECONDS AND RELEASE. (SEE OWNER'S MANUAL FOR COMPLETE DETAILS)

THE EXERCISER IS NOW SET. ALL FIVE RED LED'S WILL FLASH FOR 10 SECONDS

THEN THE UNIT WILL START, RUN THROUGH THE EXERCISE CYCLE AND SHUTDOWN.

0

If DC power to the control board is lost, the weekly exercise setting will be lost. This is indicated by all five red LEDs continually flashing. In this state the generator will still start and run in MANUAL mode, or automatically start and run if utility is lost while in AUTO mode, but it will not perform a weekly exercise cycle.

If a failure occurs while running in this mode, the five red LEDs will stop flashing, the individual fault LED will turn on and the engine will shut down. Once the AUTO/OFF/MANUAL switch has been switched to OFF, the individual fault LED will turn OFF and the five red LEDs will begin flashing to show exercise has still not been set.

3.6WEEKLY EXERCISE CYCLE

The engine control board will start and run the gen- erator once every seven days for approximately 12 minutes. If utility should fail during this exercise period, the engine control board will transfer the load to the generator output and continue to run until util- ity returns.

On the day, and at the time of day chosen for the gen- erator to exercise, set the weekly exercise cycle as fol- lows:

17

Image 19
Contents This manual should remain with the unit Introduction Authorized Service Dealer Location‹ Operation and Maintenance ‹ HOW to Obtain ServiceTable of Contents General Hazards ‹ Standards Index Electrical HazardsGenerator Transfer SwitchAutomatic Transfer Switch ATS Mode Engineered Transfer Switch Wire Start GTS ModeGenerator Fuel System ‹ 1.8.1 LOW OIL Pressure Switch‹ 1.8.2 High Coolant Temperature Switch Main Circuit BreakerLifting the Generator UnpackingFuel Consumption SpecificationsAWSF-52-C Coolant Recommendations Before InstallationEngine OIL Recommendations ‹ 2.1.2 Other Published Standards Generator LocationGenerator Mounting Support ‹ 2.1.1 Nfpa StandardsEmergency Circuit Isolation Method Basic Standby Electric SystemTotal Circuit Isolation Method Grounding the GeneratorGenerator AC Neutral Connections Connection Diagram ATS ModeConnection Diagram GTS Mode ‹ 2.11.1 Vented Batteries Battery InstallationPreparation Before START-UP Manual Transfer START-UP Control Console ComponentsBat Red Oil Red Temp Red Speed Red Crank Red Engine Governor Gain AdjustmentsAutomatic Operation Manual Retransfer ShutdownWeekly Exercise Cycle Voltage Regulator Adjustment Control Board DIP Switch SettingsIntake Manifold Procedure Exhaust Manifold ProcedureChecking Fluid Levels Cylinder Head ProcedureCooling System Overload Protection for Engine DC Electrical System‹ 4.8.1 Check Engine OIL Level ‹ 4.7.2 Battery Fluid ‹ 4.8.6 Perform Visual Inspection‹ 4.8.2 Check Battery ‹ 4.7.3 Engine Coolant‹ 4.8.13 Coolant Change Miscellaneous Maintenance‹ 4.8.11 Changing the Engine AIR Cleaner ‹ 4.9.1 Cleaning the Generator‹ 4.9.4 Battery Replacement ‹ 4.9.3 Battery MaintenancePeriodic Replacement Parts Service Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsLiquid-cooled 15, 20 and 25 kW Generators Liquid-cooled 15, 20 and 25 kW Generators Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Page Battery Post Cover Black Support Battery TrayHold Down Battery Assembly Battery TrayTo B Duct Discharge RH AL 2.5L Assy Wire 14AWG 7.5 #0 GRN/YELDoor Battery Compartment Duct Intake MID AL 2.5LPage TOP, Control Panel Switch ROC Dpst 125V SPDSwitch ROC Dpdt ON-OFF-ON Hang TAG 2 Wire Start not ShownPage Harness Ctrl PNL 2.5L Ford AL not Shown 13 17 NUT HEX M10-1.5 G8 YEL CHR Tank Coolant RecoveryEngine 2.5L Ford STARTER, 12 VoltTo Engine Bracket Fuel Regulator Body Carburetor AssemblyCover AIR Cleaner GASKET, AIR Cleaner AdapterLocktight Rotor 390 40KW 1P Direct HSB 3.9L Chrysler Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 390 25KW 1P Direct HSB 2.5L FordSaddle 2 Inch Pipe Muffler OUTPipe Exhaust 2.5L Ford Muffler 2.5L FordHarn GOV 2.5L Ford Housing Governor ConnectorCover Connector Housing ASM Motor StepperRadiator 2.5L Ford HOSE, 2.5L Ford LowerBarbed STR 1/4 NPT X 3/8 ALMInstallation Diagram MANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyThis Warranty Shall not Apply to the Following

005030-0 (15kW), 005031-0 (25kW) specifications

Generac has long been recognized as a leader in backup power solutions, and its 005031-0 (25kW) and 005030-0 (15kW) home standby generators exemplify the brand's commitment to reliability and performance. Designed for residential use, these generators provide peace of mind during outages, ensuring that homes remain powered even in the most challenging conditions.

One of the standout features of both models is their advanced Generac G-Force engine, which is engineered for longevity and impressive power output. The G-Force engine is built from the ground up for generator use, refined to handle the unique demands of continuous operation. This results in a highly durable system that requires little to no maintenance, making it a favored choice for homeowners looking for a reliable energy solution.

Another important characteristic is the True Power technology featured in both generators. This technology delivers clean, stable power that is safe for sensitive electronics and appliances. It ensures that devices such as computers and medical equipment operate smoothly without the risk of damage from power fluctuations. Additionally, the Generac 005031-0 and 005030-0 generators are equipped with the Quiet-Test mode, allowing them to run at lower RPMs during routine weekly self-tests. This innovation significantly reduces the noise produced during tests, making it less disruptive for residents.

Furthermore, these generators come with a user-friendly interface and a mobile link app, enabling homeowners to monitor their generator's performance remotely via a smartphone. This feature enhances convenience, allowing users to receive alerts and notifications about their generator's status, maintenance needs, and operation conditions right from their devices.

Both the 25kW and 15kW models are also designed with a robust transfer switch, which seamlessly shifts power from the grid to the generator in case of any outages. This automatic transfer feature ensures that homes maintain power without needing manual intervention, making them ideal for those who want uninterrupted electricity.

In terms of fuel source, both models operate on natural gas or propane, providing flexibility to homeowners regarding fuel availability and preferences. With excellent warranty options and Generac's reputation for quality, both the 005031-0 (25kW) and 005030-0 (15kW) generators stand as dependable choices for safeguarding homes from the unpredictability of power outages.