Begin by locating the auto prime adjustment wheel. It protrudes from the secondary regulator mounted on the generator and is often covered by a red vinyl cap. The adjustment knob is orange and just below the knob is a gold colored washer. To adjust, hold the washer and rotate the orange knob counterclockwise to lean the adjustment. Try this adjustment hot and cold.

In all multi-cylinder engines, the device may be disabled in lieu of adjustment.

Main Mixture

The main mixture is located on the secondary regulator and is a very large brass screw and lock nut.

Begin by loosening the lock nut and counting the turns until the screw just seats. Record this number so that you may return to it later. REMEMBER, the generator DID run previously either at the factory or at the site.

Proceed by disconnecting the generator set’s Auto Prime (if so equipped) by unplugging the terminal on the orange wire.

Check that all fuel supply lines are turned on (where applicable).

Check that he generator’s main line output breaker is turned OFF (where applicable).

The next step is to start the generator. Voltage will be available at the output terminals and anywhere the generator is connected. Think ahead and warn others of your intentions.

Operate the generator with the operation switch in the “Manual-Run” mode. The engine should begin cranking.

While the engine is cranking, turn the main adjustment screw counterclockwise until the engine starts. Continue to rotate back and forth until smooth operation is obtained. [ Adjustments that are too rich (too far counterclockwise) or too lean (too far clockwise) will result in the same rough sound. Use slow, rotating motion to find the smoothest spot.]

Once set, energize the AC breaker and apply available load. Readjust main mixture screw until generator (with or without applied load) is smooth. This will most likely be a slight rotation richer than initial setting at no load.

Shut off engine by placing the Operation Switch into the “OFF” position.

If operation problems persist, contact your dealer or call Baldor Generators for Technical Support at (920) 236-4200.

Page 28 of 45

Image 35
Contents Model AE12 Generator Automatic Emergency Powr ProductsSafety Warnings Page Page Page Table of Contents Customer Connection Wiring Diagram AE12 Base Outline Drawing Forward Specifications for Your AE12 bBALDOR Generator SET Location Connection Information Page Engine Information Inspecting MaintenanceGenerator END Maintenance CleaningAdjustments Engine MaintenanceStorage or Long Term NON-USAGE Ordering Parts ServiceSafety Considerations General Installation & Site Selection GuidelinesMiscellaneous Considerations Cooling ConsiderationsNoise Considerations Remote Start Connections Electrical Installation GuidelinesUnits with Factory Installed Enclosure AC Power ConnectionsUnits Without Enclosure Page Gaseous Fuel Supply Piping Gaseous Fuel InformationLP Cylinder Tanks Primary Regulator not suppliedSecondary Regulator supplied LP TanksManual Fuel Valves Fuel valvesElectric fuel shut-off valves Pipe Capacity in Cubic Feet Propane GAS Flow ChartNatural GAS Flow Chart Controls and Their Functions Master Control SwitchOperation Prior to Starting the UnitCircuit Breaker Fault Indicator LightFuse for the Control Logic Board Possible Problems Simple TroubleshootingLOW Voltage Output Initial Checks Troubleshooting for Gaseous Fuel SystemBasic Description Order of Occurrence AdjustmentsProblems and Possible Solutions Page GO to Starter Solenoid on Engine Generator Fails to StartPage Abbreviations AE Series InterconnectionPage Page Page Page Page Page Page Page Page For AE12 Units with Enclosure Limited Warranty Owner’s Responsibilities Page California Proposition 65 Warning