Remote/Auto Mode: This is the position you need to have the Master Control Switch set in when you wish to operate the Generator Set automatically in conjunction with a Transfer Switch. This way, the generator set can only be started by making a connection across the remote start connection points on the terminal block located in the control box.

Should this remote start connection be opened up while the engine is running the engine will shut down after a 60-90 second 'Cool Down' time delay.

The engine can be shut down immediately from this position by putting the Master Control Switch into the 'OFF' position.

A fault condition will also shut the engine down immediately.

Fault Indicator Light:

This circular Red indicator light will come on in conjunction with the engine shutting down whenever a fault condition develops.

One Fault Condition that will cause a shut down is if the engine's starter motor cranks for more than 30 seconds without the engine starting. This fault shutdown is to prevent damage to the starter motor.

Another Fault Condition will develop if the generator set stops producing power while the engine is running. This fault shutdown is to prevent further potential damage to the generator end itself.

Another Fault Condition will develop if the engine's Low Oil Pressure Protection System shuts the engine down.

To reset the Control Logic once a Fault Condition has occurred, you must put the Master Control Switch onto the 'OFF' position for a minimum of 10 seconds.

Fuse for the Control Logic Board:

This fuse is rated at 1 Amp. It's purpose is to prevent excessive and potentially damaging current from getting to the circuit board.

Circuit Breaker:

The Circuit Breakers on the generator set provide overload protection for the generator set. These Breakers protect the generator set against potential damage from excessive AC current.

Page 23 of 45

Image 30
Contents Automatic Emergency Powr Products Model AE12 GeneratorSafety Warnings Page Page Page Table of Contents Customer Connection Wiring Diagram AE12 Base Outline Drawing Forward Specifications for Your AE12 bBALDOR Generator SET Location Connection Information Page Engine Information Cleaning MaintenanceGenerator END Maintenance InspectingEngine Maintenance AdjustmentsStorage or Long Term NON-USAGE Service Ordering PartsGeneral Installation & Site Selection Guidelines Safety ConsiderationsCooling Considerations Noise ConsiderationsMiscellaneous Considerations Electrical Installation Guidelines Remote Start ConnectionsAC Power Connections Units with Factory Installed EnclosureUnits Without Enclosure Page Gaseous Fuel Information Gaseous Fuel Supply PipingLP Tanks Primary Regulator not suppliedSecondary Regulator supplied LP Cylinder TanksFuel valves Electric fuel shut-off valvesManual Fuel Valves Propane GAS Flow Chart Pipe Capacity in Cubic FeetNatural GAS Flow Chart Prior to Starting the Unit Master Control SwitchOperation Controls and Their FunctionsFault Indicator Light Fuse for the Control Logic BoardCircuit Breaker Simple Troubleshooting Possible ProblemsLOW Voltage Output Troubleshooting for Gaseous Fuel System Basic DescriptionInitial Checks Adjustments Problems and Possible SolutionsOrder of Occurrence Page Generator Fails to Start GO to Starter Solenoid on EnginePage AE Series Interconnection AbbreviationsPage Page Page Page Page Page Page Page Page For AE12 Units with Enclosure Limited Warranty Owner’s Responsibilities Page California Proposition 65 Warning