ERP2U Power Supply Design Guide, V1.0
5.8AC Line Transient Specification
STATUS
Recommended
AC line transient conditions shall be defined as “sag” and “surge” conditions. Sag conditions (also referred to as “brownout” conditions) will be defined as the AC line voltage dropping below nominal voltage. Surge conditions will be defined as the AC line voltage rising above nominal voltage.
The power supply shall meet the requirements under the following AC line sag and surge conditions.
Table 4: AC Line Sag Transient Performance
AC Line Sag
Duration | Sag | Operating AC Voltage | Line Frequency | Performance Criteria |
|
|
|
|
|
Continuous | 10% | Nominal AC Voltage ranges | 50/60 Hz | No loss of function or performance |
|
|
|
|
|
0 to 1 AC | 100% | Nominal AC Voltage ranges | 50/60 Hz | No loss of function or performance |
cycle |
|
|
|
|
|
|
|
|
|
>1 AC cycle | >10% | Nominal AC Voltage ranges | 50/60 Hz | Loss of function acceptable, self |
|
|
|
| recoverable |
|
|
|
|
|
Table 5: AC Line Surge Transient Performance
AC Line Surge
Duration | Surge | Operating AC Voltage | Line Frequency | Performance Criteria |
|
|
|
|
|
Continuous | 10% | Nominal AC Voltages | 50/60 Hz | No loss of function or performance |
|
|
|
|
|
0 to ½ AC | 30% | 50/60 Hz | No loss of function or performance | |
cycle |
| Voltages |
|
|
|
|
|
|
|
5.9AC Line Fast Transient Specification
STATUS
Recommended
The power supply shall meet the
∙These input transients must not cause any
∙The
∙The supply must meet