Intel ERP2U manual AC Line Transient Specification, AC Line Fast Transient Specification

Page 12

SSI

ERP2U Power Supply Design Guide, V1.0

5.8AC Line Transient Specification

STATUS

Recommended

AC line transient conditions shall be defined as “sag” and “surge” conditions. Sag conditions (also referred to as “brownout” conditions) will be defined as the AC line voltage dropping below nominal voltage. Surge conditions will be defined as the AC line voltage rising above nominal voltage.

The power supply shall meet the requirements under the following AC line sag and surge conditions.

Table 4: AC Line Sag Transient Performance

AC Line Sag

Duration

Sag

Operating AC Voltage

Line Frequency

Performance Criteria

 

 

 

 

 

Continuous

10%

Nominal AC Voltage ranges

50/60 Hz

No loss of function or performance

 

 

 

 

 

0 to 1 AC

100%

Nominal AC Voltage ranges

50/60 Hz

No loss of function or performance

cycle

 

 

 

 

 

 

 

 

 

>1 AC cycle

>10%

Nominal AC Voltage ranges

50/60 Hz

Loss of function acceptable, self

 

 

 

 

recoverable

 

 

 

 

 

Table 5: AC Line Surge Transient Performance

AC Line Surge

Duration

Surge

Operating AC Voltage

Line Frequency

Performance Criteria

 

 

 

 

 

Continuous

10%

Nominal AC Voltages

50/60 Hz

No loss of function or performance

 

 

 

 

 

0 to ½ AC

30%

Mid-point of nominal AC

50/60 Hz

No loss of function or performance

cycle

 

Voltages

 

 

 

 

 

 

 

5.9AC Line Fast Transient Specification

STATUS

Recommended

The power supply shall meet the EN61000-4-5directive and any additional requirements in IEC1000-4-5:1995and the Level 3 requirements for surge-withstand capability, with the following conditions and exceptions:

These input transients must not cause any out-of-regulation conditions, such as overshoot and undershoot, nor must it cause any nuisance trips of any of the power supply protection circuits.

The surge-withstand test must not produce damage to the power supply.

The supply must meet surge-withstand test conditions under maximum and minimum DC-output load conditions.

- 12 -

Image 12
Contents SSI Disclaimer Contents Tables Agency RequirementsPurpose Conceptual OverviewDefinitions/Terms/Acronyms RequiredMechanical Overview Required OptionalOptional Chassis Mounting Features Airflow RequirementsOptional RecommendedTemperature Requirements AC Inlet ConnectorAC Input Requirements Redundant AC InletsAC Input Voltage Specification Output Minimum Power EfficiencyEfficiency AC Input RatingAC Line Dropout AC Line FuseAC Inrush AC Line Transient Specification AC Line Fast Transient SpecificationAC Line Sag Transient Performance AC Line Surge Transient PerformanceDC Output Specification Output ConnectorsRequired Baseboard power connector Optional Processor Power ConnectorRequired Peripheral Power Connectors Required Floppy Power ConnectorPeripheral Power Connectors P9 Floppy Power ConnectorOptional Server Signal Connector Server Signal ConnectorGrounding Remote SenseOutput Power/Currents 350 W Load RatingsVoltage Minimum Continuous Maximum Continuous Peak 480 W Load RatingsVoltage Regulation Standby OutputsVoltage Regulation Limits Dynamic Loading Capacitive LoadingRipple / Noise Transient Load RequirementsRedundancy Hot Swap RequirementsRipple and Noise +3.3 +12 +5 VSBSSI Timing Requirements Output Voltage TimingDescription Turn On/Off Timing Recommended DescriptionTurn On/Off Timing Protection Circuits Current Limit240VA Protection Over Current ProtectionOver Temperature Protection Over Voltage ProtectionOver Voltage Limits Output VoltageControl and Indicator Functions Pson # Signal Characteristic Signal TypePwok delay PSON#Pwok Power OK Pwok Signal CharacteristicsField Replacement Unit FRU Signals SMBus CommunicationModule FRU Data Module FRU Data Format Product Info AreaMultiRecord Area Field Name PS Info Field Information DefinitionLED Indicators LED IndicatorsPower Supply LEDs Mtbf 10Agency Requirements