Fluke 875 manual Installation, Readout Module, Pull Box

Page 15

Installation

Installation 2

Section 2

Installation

2.1 Installation

Installation of the monitoring system consists of selecting suitable mounting sites for each component of the system, mounting each of the components, and connecting the components into the system configuration.

Installation of this system is as follows:

NOTE

Refer to the applicable drawings in Appendix C for further installation Instructions.

Rack Chassis

The 876-1-55 Rack Chassis is a standard 19-inch chassis with a flame barrier. When seismic qualification is required for the readout, seismic support brackets (P/N 876-1-114) are needed to support the rear of the rack chassis. The brackets are designed to mount on the 19-inch qualified equipment rack. Recommended mounting is shown on drawings GEL876-1-55, and 876-1-114.

Readout Module

Readout Module 876A-1 is designed to fit into one-half of an 876-1-55 Rack Chassis. Insert the readout module in the rack chassis (see drawing GEL876A-1), then insert and tighten the two holding screws in the rear flanges of the rack chassis. The pawl fastener on the front panel of the readout must be tightened.

Optical Isolator (No longer manufactured, consult factory)

Detector

NOTE

The detector case MUST BE PHYSICALLY GROUNDED TO EARTH GROUND. The readout instrument circuit common SHOULD NOT be grounded to earth ground.

The 877-1 Detector is designed to mount on the containment wall. A mounting bracket attached to the detector has four holes that are used for mounting. Studs must be placed in the containment wall before mounting the detector. Dimensions for the studs are the same as the dimensions of the holes in the mounting bracket (refer to drawing GEL877-1). Recommended studs are 5/16 inch Grade 5. No lock washers are to be used and recommended torque for the nuts is 18 ft. lbs. Orient the detector so that the cable connectors are on the underside. Attach the detector to the mounting bracket with the four clamps provided, securing the bolts with a torque of 132 in. lbs. (Figure 1-5 and GEL877-1).

Pull Box

A cable pull box is required to allow for thermal expansion of the detector cables and to provide a service loop. The pull box (drawing 878-12-5) is a typical type that mounts to the containment wall. It should be mounted directly below the detector as shown in Figure 1-1. Depending on actual detector location, more than one pull box may be necessary.

2-1

Image 15
Contents High Range Containment Monitor VictoreenFluke Biomedical Table of Contents Calibration and Test Procedures Containment Monitor SpecificationsIntroduction General DescriptionReadout Module 876A-1 Temperature Operating 40 to 120F 4 to 49CEquipment Overview High-Range Containment Monitor DetectorRack Chassis Optional Equipment Pull Box AssemblyCables/Connectors/Panel Flexible Tubing 878-12-30TABHigh-Range Containment Monitor Typical Energy Response Curve Detector Typical Linearity Detector Receiving Inspection High-Range Detector, Recommended InstallationStorage Procedures, Warnings, and CautionsBlank Pull Box InstallationInstallation Readout ModuleCable Sealing Specifications for CableDetector Cable Inside Containment Cable and Wiring InstallationDetector Test After Installation Specifications for CableComputer & Recorder Ancillary WiringAll Alarms on P2 Normal Operation Shelf State Power Connections P1Operation OperationVictoreen Function Description Functional DescriptionReadout Module 876A-1 Negative Power Supply High Voltage Power Supply Normal Operation non-ECS Test FAIL/SAFE Comparison Circuit on Power Supply BoardOperation of High Voltage Supply During ECS Test Alert Alarm Circuit High Alarm CircuitFail/Safe Circuit Recorders and Computer BuffersPen Clamp Meter at extreme lower end of scale Panel Meter Action During ECS TestAction of Green Safe/Reset Light and Alarm During ECS Test Low Voltage Ramp GeneratorMonitoring Circuits of The ECS Board Block Diagram of ECS Test Muting Circuits of ECS Board Safe/Reset Sub-circuitsBlank Maintenance, Calibration, and Troubleshooting MaintenanceCalibration Test Procedure TP876A-1-108 Troubleshooting Rear Panel Signal Input CircuitMother Board P/N 876-1-78, Schematic 876-1-3A PreamplifierIMeter Board P/N 876A-1-86, Schematic 876A-1-3ETest Point Normal Channel Test TP501 TP502 +6.3High Alarm Circuit Muting Stages of the Alarm CircuitsNormal Low Signal Level Channel Test ESC Board P/N 876A-1-92, Schematic 876A-1-3D Wave Shapes on the Electronic Check Source Board Starting With Pins M and P on the Power Supply Schematic Overall Fail Circuitry Associated with the ECS TestStarting With Terminal H on Relay Driver Board Operation of the Latch Circuit Outputs of U206 Pulse Generator on the ECS BoardCircuit assumed initially in Pass Condition Fail Condition Latch CircuitPin Voltage State Comments NORCalibration and Test Procedures Blank Cable and Pull Box Procedures Cable and Pull Box ProceduresVictoreen Applicable Drawings and Bill of Materials Applicable DrawingsDocument Number Description Detector Cable Out of Containment Applicable Bill of Materials Fluke Biomedical