Victoreen 875
Operators Manual
NOTE
Under potential L.O.C.A. conditions of pressure and temperature, the cable may expand as much as 11 inches per 100 feet.
The distance from the pull box to the detector will be determined by the amount of flex hose used to seal the detector cables. Additional information is found in the paragraph below Cable Sealing and in CABLE- 877 and
Once the cables have been pulled and tested, the pull box cover must be bolted shut. To bolt the pull box shut, follow the steps outlined in procedure
Cable Sealing
Specifications for Cable 878-1-9
Conductor | #24 AWG, 19/36 Tinned Copper |
Insulation | Tefzel (BIWF) |
Shield | #36 AWG, Tinned copper brand, 90% Coverage |
Jacket | Tefzel (BIWF) |
Outside Diameter | 0.250 to 0.295 in |
| (6.35 to 7.49 mm) |
Impedance | 75 ohms nominal |
Capacitance | 22 pf/ft nominal |
Dielectric Strength | 7000 V minimum |
Operating Voltage | 2300 V maximum |
The following guidelines are based on the sealing method used during the qualification test. Stainless steel Flex Hose
NOTE
Seismic support and the sealing technique at penetration vary with plant requirements. Techniques and materials used are the customer's responsibility.
Attach the stainless steel tubing to the pull box with compression fittings (¾ inch) and, after finger tightening, tighten at least