Emerson 610 installation manual Wiring Connections

Page 33

Wiring Connections

6.The UPS System Control Cabinet (SCC) neutral must be connected to one common point and solidly grounded per requirements of the National Electrical Code. The ground connection inside the UPS SCC/switchgear cabinet may be required by the power wiring configuration at your site.

! CAUTION

UPS bypass and system output neutral must be connected to only one common point in the UPS system. This neutral line must be grounded at the source. Refer to 6.0 - Configuring Your Neutral and Ground Connections for further details.

7.For battery systems: DC power cables (and ground) from battery to UPS module and between battery cabinets/strings. Observe polarity. When multiple conduits are used, an equal number of positive and negative cables should be contained in each conduit.

NOTE

DC power and battery circuit breaker control cables are provided with Liebert battery cabinets for use between multiple cabinets when bolted together. Power cables are sized for interconnecting battery cabinets. Battery cabinets specified for bolting up to the UPS are shipped with power cables to connect the battery cabinet system to the UPS module. Field- supplied cabling must be provided to connect stand-alone battery cabinets to the UPS module. Connections from the final battery cabinet to the UPS are provided in the field.

! WARNING

Do not make any connections between battery tiers in the battery cabinet. These connections will be made by the Liebert Global Services representative during start-up.

8.For remote battery: Install DC power cables (and ground) from battery to Module Battery Disconnect, and then to UPS Module DC bus. Observe polarity.

! CAUTION

Cables between batteries and the UPS should be run in matched pairs, positive-with-negative, within each conduit or cable run. Grouping like-polarity cables together (i.e., positive-with-positive and negative-with-negative) can cause stress or damage to the cables, conduit or buswork.

9.Module Battery Disconnect control wiring to UPS module and between battery cabinets, if applicable. Wiring must be run in individual separate steel conduit.

10.Control wiring from System Control Cabinet (SCC) to UPS modules. Wiring must be run in individual separate steel conduit. Refer to Figures 60 through 62 or your submittal drawings.

11.Control connections between the System Control Cabinet (SCC) and the Maintenance Bypass panelboard or switchgear. Refer to Figure 67 or your submittal drawings.

12.Control wiring to the optional Remote Monitor Panel, if used. Selected alarm messages are also available for customer use through a set of contacts on an optional separate terminal board. Wiring must be run in individual separate steel conduit.

13.Emergency Power Off control wiring (to SCC) must be run in separate steel conduit.

14.Optional communications wiring (to SCC) for terminals, site monitoring or modem must be run in separate steel conduit.

15.Any additional special wiring required at your site. Refer to Figures 58 through 74 or your submittal drawings.

27

Image 33
Contents Liebert Series 610 UPS Contacting Liebert for Support Battery Cabinet PrecautionsTable of Contents Figures Iii Tables Important Safety Instructions Page Installation Considerations Multi-Module 500 to 750kVA UPS System Control Cabinets Types of System Control CabinetsUnloading and Handling External Inspections Internal Inspections and Shipping Material RemovalInspections Equipment Location Battery Installation Battery Safety PrecautionsAvertissement Battery Safety Precautions in French Per CSA RequirementsBattery Cabinets Open-Rack Batteries Configuring Your Neutral and Ground Connections Preferred grounding configuration, wye-connected service Preferred Grounding Configuration, Wye-Connected ServiceAlternate grounding configuration, wye-connected service Alternate Grounding Configuration, Wye-Connected ServicePreferred grounding configuration with isolated bypass Preferred Grounding Configuration With Isolated BypassAlternate grounding configuration, non-isolated Alternate Grounding Configuration, Non-IsolatedConfiguring Your Neutral and Ground Connections Preferred grounding configuration, impedance-grounded wye Preferred grounding configuration, battery systems Preferred Grounding Configuration, Battery SystemsWiring Considerations Power Wiring Scct Abbreviations for circuit breakers Control WiringBattery Wiring Specific Connections Wiring ConnectionsWiring Connections Power wiring terminals, factory supplied Wiring InspectionField-supplied lugs 16, National Electrical Code Reprint Installation Drawings 97-797600-176 Rev 88-797658-84 Rev 88-797658-94 Rev 88-797657-26 Rev 88-797657-95 Rev Outline drawing, 500kVA Multi-Module UPS, 12-pulse rectifier 88-797657-92 Rev 88-797668-84 Rev 88-797668-90 Rev 88-797665-29 Rev 88-797665-90 Rev 88-797656-66 Rev 88-797656-86 Rev 88-797668-66 Rev 88-797668-86 Rev 88-797664-68 Rev 88-797664-88 Rev 88-797677-65 Rev Base mounting patterns, 500kVA module, 6-pulse rectifier Base mounting patterns, 500kVA module, 12-pulse rectifier 88-797613-28 Rev Base mounting patterns, 625-750kVA module, 6-pulse rectifier 88-797613-29 Rev 88-797613-19 Rev 88-797613-27 Rev Shipping split detail, 500kVA, 12-pulse rectifier 88-797612-08 Rev Shipping split detail, 625-750kVA, 6-pulse rectifier 88-797612-09 Rev Shipping split detail, 625-750kVA, 12-pulse rectifier 88-797612-07 Rev Battery power pack system Battery power pack, Size a 88-797607-63 Rev Outline drawing, System Control Cabinet SCCT, 200-1200A 88-797613-71 Rev Outline drawing, System Control Cabinet SCCT, 1600-2000A 88-797613-78 Rev Outline drawing, System Control Cabinet SCCT, 2500-3000A 88-797613-73 Rev Outline drawing, System Control Cabinet SCCT, 4000A Base mounting patterns, System Control Cabinet SCCT, 4000A 96-797619-58A Rev 96-797619-66A Rev Control connection location diagram, Scct 96-797619-51A Rev 96-797619-60 Rev 96-797619-19A Rev 96-797619-20 Rev 96-797619-21 Rev 96-797619-130 Rev 96-797619-28 Rev 96-797619-128 Rev 96-797619-62 Rev 96-797619-90 Rev 96-797619-91 Rev 96-797619-52A Rev 96-797619-53A Rev 96-797619-54A Rev 96-797619-55A Rev 96-797619-56A Rev 96-797619-57A Rev 88-797616-09 Rev 88-797616-13 Rev 88-797616-07 Rev Outline drawing, remote status panel, surface mount Installation Drawings Data, Series 610, 500-750kVA, Multi-Module Systems Site planning data-600V input Site planning data-480V input System Control Cabinets Page Page Page Environmental Systems 800-543-2778 Outside the United States