Emerson 610 installation manual Field-supplied lugs

Page 35

 

 

 

 

 

 

 

 

 

Wiring Inspection

 

Table 4

Field-supplied lugs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

One-Hole Lugs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T & B1 Lug Style

Wire Size

Bolt Size (in.)

Tongue Width (in.)

T & B1 P/N

 

Liebert P/N

 

1

 

 

 

#1 AWG

3/8

0.76

H973

 

12-714255-46

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

1/0 AWG

3/8

0.88

J973

 

12-714255-56

 

 

 

 

Stak-On

 

 

 

 

 

 

 

3

 

 

2/0 AWG

3/8

1.00

K973

 

12-714255-66

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

3/0 AWG

3/8

1.10

L973

 

12-714255-76

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

4/0 AWG

3/8

1.20

M973

 

12-714255-86

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

#1 AWG

3/8

0.75

60124

 

 

 

 

 

Color-Keyed

 

 

 

 

 

 

 

7

 

 

1/0 AWG

3/8

0.88

60130

 

 

 

 

 

Aluminum/

 

 

 

 

 

 

 

8

 

 

2/0 AWG

3/8

0.97

60136

 

 

 

 

Copper

 

 

9

 

 

 

3/0 AWG

3/8

1.06

60142

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

#1 AWG

5/16

0.67

54947BE

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

1/0 AWG

3/8

0.75

54909BE

 

 

 

 

 

Color-Keyed

 

 

 

 

 

 

 

12

 

 

2/0 AWG

3/8

0.81

54910BE

 

 

 

 

 

Copper Cable

 

 

 

 

 

 

 

13

 

 

3/0 AWG

1/2

0.94

54965BE

 

 

 

 

Long Barrel

 

 

14

 

 

 

4/0 AWG

1/2

1.03

54970BE

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

250 MCM

1/2

1.09

54913BE

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

Narrow-Tongue

350 MCM

1/2

1.09

55165

 

 

17

 

 

Copper Cable

500 MCM

1/2

1.20

55171

 

 

 

 

 

 

 

 

 

 

 

1.

Manufacturer: Thomas & Betts (T & B), 1-800-862-8324

 

 

 

 

29

Image 35
Contents Liebert Series 610 UPS Contacting Liebert for Support Battery Cabinet PrecautionsTable of Contents Figures Iii Tables Important Safety Instructions Page Installation Considerations Multi-Module 500 to 750kVA UPS System Control Cabinets Types of System Control CabinetsUnloading and Handling Inspections External InspectionsInternal Inspections and Shipping Material Removal Equipment Location Battery Installation Battery Safety PrecautionsAvertissement Battery Safety Precautions in French Per CSA RequirementsBattery Cabinets Open-Rack Batteries Configuring Your Neutral and Ground Connections Preferred grounding configuration, wye-connected service Preferred Grounding Configuration, Wye-Connected ServiceAlternate grounding configuration, wye-connected service Alternate Grounding Configuration, Wye-Connected ServicePreferred grounding configuration with isolated bypass Preferred Grounding Configuration With Isolated BypassAlternate grounding configuration, non-isolated Alternate Grounding Configuration, Non-IsolatedConfiguring Your Neutral and Ground Connections Preferred grounding configuration, impedance-grounded wye Preferred grounding configuration, battery systems Preferred Grounding Configuration, Battery SystemsWiring Considerations Power Wiring Scct Abbreviations for circuit breakers Control WiringBattery Wiring Specific Connections Wiring ConnectionsWiring Connections Power wiring terminals, factory supplied Wiring InspectionField-supplied lugs 16, National Electrical Code Reprint Installation Drawings 97-797600-176 Rev 88-797658-84 Rev 88-797658-94 Rev 88-797657-26 Rev 88-797657-95 Rev Outline drawing, 500kVA Multi-Module UPS, 12-pulse rectifier 88-797657-92 Rev 88-797668-84 Rev 88-797668-90 Rev 88-797665-29 Rev 88-797665-90 Rev 88-797656-66 Rev 88-797656-86 Rev 88-797668-66 Rev 88-797668-86 Rev 88-797664-68 Rev 88-797664-88 Rev 88-797677-65 Rev Base mounting patterns, 500kVA module, 6-pulse rectifier Base mounting patterns, 500kVA module, 12-pulse rectifier 88-797613-28 Rev Base mounting patterns, 625-750kVA module, 6-pulse rectifier 88-797613-29 Rev 88-797613-19 Rev 88-797613-27 Rev Shipping split detail, 500kVA, 12-pulse rectifier 88-797612-08 Rev Shipping split detail, 625-750kVA, 6-pulse rectifier 88-797612-09 Rev Shipping split detail, 625-750kVA, 12-pulse rectifier 88-797612-07 Rev Battery power pack system Battery power pack, Size a 88-797607-63 Rev Outline drawing, System Control Cabinet SCCT, 200-1200A 88-797613-71 Rev Outline drawing, System Control Cabinet SCCT, 1600-2000A 88-797613-78 Rev Outline drawing, System Control Cabinet SCCT, 2500-3000A 88-797613-73 Rev Outline drawing, System Control Cabinet SCCT, 4000A Base mounting patterns, System Control Cabinet SCCT, 4000A 96-797619-58A Rev 96-797619-66A Rev Control connection location diagram, Scct 96-797619-51A Rev 96-797619-60 Rev 96-797619-19A Rev 96-797619-20 Rev 96-797619-21 Rev 96-797619-130 Rev 96-797619-28 Rev 96-797619-128 Rev 96-797619-62 Rev 96-797619-90 Rev 96-797619-91 Rev 96-797619-52A Rev 96-797619-53A Rev 96-797619-54A Rev 96-797619-55A Rev 96-797619-56A Rev 96-797619-57A Rev 88-797616-09 Rev 88-797616-13 Rev 88-797616-07 Rev Outline drawing, remote status panel, surface mount Installation Drawings Data, Series 610, 500-750kVA, Multi-Module Systems Site planning data-600V input Site planning data-480V input System Control Cabinets Page Page Page Environmental Systems 800-543-2778 Outside the United States